Acs580-0P; Installation - ABB ACS580-0P Supplement Installation Manual

Enclosed drives (230v, 1-100 hp; 480v, 1-200 hp; 575, 2-150 hp)
Hide thumbs Also See for ACS580-0P:
Table of Contents

Advertisement

10

ACS580-0P

Installation

This information is unique to ACS580 input disconnect configurations (0P or
0P+F255). The ACS580 with Input Disconnect is an ACS580 AC adjustable
frequency drive packaged with an input disconnect switch or circuit breaker. Refer to
the Installation instructions on page 8, for all other information. Failure to observe
the warnings and instructions may cause malfunction or personal hazard.
WARNING! Before you begin read
WARNING! When the ACS580 with Input Disconnect is connected to the line power,
the Motor Terminals T1, T2, and T3 are live even if the motor is not running. Do not
make any connections when the ACS580 with Input Disconnect is connected to the
line. Disconnect and lock out power to the drive before servicing the drive. Failure to
disconnect power may cause serious injury or death.
1. Install wiring
WARNING!
• Metal shavings or debris in the enclosure can damage electrical equipment and
create a hazardous condition. Where parts, such as conduit plates require cutting or
drilling, first remove the part. If that is not practical, cover nearby electrical
components to protect them from all shavings or debris.
• Do not connect or disconnect input or output power wiring, or control wires, when
power is applied.
• Never connect line voltage to drive output Terminals T1, T2, and T3.
• Do not make any voltage tolerance tests (Hi Pot or Megger) on any part of the unit.
Disconnect motor wires before taking any measurements in the motor or motor
wires.
• Make sure that power factor correction capacitors are not connected between the
drive and the motor.
Enclosure Designation
Px1-1 & Px12-1
Px1-2 & Px12-2
Px1-3 & Px12-3
Px1-4 & Px12-4
PxB3R-1
PxB3R-2
PxB1-3 & PxB12-3
1)
100 HP @ 230V.
2)
* Only available as ACS580 R2 Frame
ACS580-0P
Supplemental Installation Manual for ACS580-0P
Safety instructions
Horsepower Range by Voltage
208V
460V
1 to 5 HP
1 to 7.5 HP
10 HP
10 to 15 HP
15 to 20 HP
20 to 30 HP
25 HP
40 to 60 HP
1 to 10 HP
1 to 15 HP
15 to 25 HP
20 to 60 HP
1
30 to 100 HP
75 to 200 HP
on page 4.
Base Drive
Frame
2
575V
N/A
R1
2 to 15 HP
R2
20 to 30 HP
R3
N/A
R4
2 to 15 HP
R1-R2
20 to 30 HP*
R3-R4
40 to 150 HP
R5-R8

Advertisement