Mounting The Module; Location Recommendations; Operating Environment Requirements; Mounting Recommendations - Trane Tracer MP503 Installation, Operation And Maintenance Manual

Input/output module
Hide thumbs Also See for Tracer MP503:
Table of Contents

Advertisement

Mounting the Module

This Section provides information about the following:

Location Recommendations

Trane recommends locating the MP503:

Operating Environment Requirements

Operate the MP503 in an environment that meets the following requirements:

Mounting Recommendations

Important:
Mounting recommendations are as follows:
Figure 4.
10
Location recommendations
Operating environment requirements
Mounting recommendations
Near the controlled equipment to reduce wiring costs
Where it is easily accessible for service personnel
Where public access is restricted to minimize the possibility of tampering or vandalism
Temperature: –40°F to 158°F (–40°C to 70°C)
Relative humidity: 5–95%, non-condensing
Leave the cover on when mounting the MP503 to avoid the possibility damaging the
circuit board during installation.
Mount the module in any direction, other than with the front of the cover facing downward.
Mount using the two 3/16 in. (4.8 mm) radius mounting holes provided (refer to
Mounting fasteners are not included.
Attach the module securely so it can withstand vibrations of associated heating, ventilating,
and air-conditioning (HVAC) equipment.
If the module is mounted in a small enclosed compartment, complete all wiring connections
before securing the module in the compartment.
Mounting the MP503
Figure
4).