Example 3: Control A Binary Output On The Mp503 From A Mp581 - Trane Tracer MP503 Installation, Operation And Maintenance Manual

Input/output module
Hide thumbs Also See for Tracer MP503:
Table of Contents

Advertisement

Network Variable Bindings
of the SNVT that matches the variable selected in the MP503.
between the MP503 and MP581 #2.
Table 4.
1
2
(a) The MP581 has 40 generic temperature (SNVT_temp_p) network variable inputs available for binding (nviTemp01 through
(b) The MP581 has 40 generic temperature (SNVT_temp_p) network variable inputs available for binding (nviTemp01 through
After completing the bindings, program Tracer MP581 #2 to calculate enthalpy from the outside air
temperature and humidity.\
Important:

Example 3: Control a Binary Output on the MP503 from a MP581

This example shows an nvi on the MP503 being bound, which allows a binary output on the MP503
to be controlled by another device on the LonTalk network. In this example, binary output 1 on the
MP503 is starting and stopping an exhaust fan. The MP503 is communicating via the LonTalk
network to a MP581 that is controlling an AHU. The AHU and the exhaust fan follow the same
schedule; for example, whenever the AHU runs, the exhaust fan runs.
Bind an nvo on the MP581 to an nvi on the MP503 so the AHU and exhaust fan run together.
shows the LonTalk network for this example.
Figure 8.
18
Bindings for example 2
Network Variable Output on the
MP503
nvoTemperature1
nvoCurrent2
The Tracer MP581 has 40 generic temperature (SNVT_temp_p) network variable inputs available for
binding (nviTemp01 through nviTemp40).
The Tracer MP581 has 8 generic current (SNVT_amp_mil) network variable inputs available for binding
(nviCurrent_mA01 through nviCurrent_mA08).
nviTemp40).
nviTemp40).
Custom programming is required to display this data on the operator display of
Tracer MP581 #2. Remember that the outside air humidity is being transmitted over
the network in units of mA. Some custom programming is required in Tracer MP581
#2 to convert the humidity from units of mA to units of percent (%) before performing
the enthalpy calculation.
LonTalk network for example 3
Tracer MP581 with
operator display
Binding To
Tracer MP503
LonTalk link
Table 4
shows the bindings required
Network Variable Input on the
MP581 #2
(a)
nviTemp01
nviCurrent_mA01
®
Additional
LonTalk
devices
CNT-SVX09E-EN
(b)
Figure 8