The AM-1000 is a fire detection control panel with the following main features:
•
Microprocessor System
•
1 analog line
•
99 detectors + 99 input/output modules
•
LCD graphic display with 8 lines for 20 columns (128 x 64 points)
•
Keyboard with dedicated key for particular functions:
Evacuation , Delays reset, Buzzer silence, Siren silence/restore, Reset.
•
1 RS – 232 interface for the connection of a remote serial printer (80 characters per line).
•
UP/DOWNLOAD software: option to the printer on RS-232 line.
•
Optional Tel. Dialer Board to be installed outside the panel cabinet.
•
Power supply : 24Vdc – 1,4 A
•
Battery charger : 0,45 A
•
User power connection to supply external devices ( for example : sirens, bells, etc. )
•
One supervised control for sirens
•
Wall mounting type for panel cabinet
•
3 password levels: (User - Maintenance – Configuration).
•
Programmable text labels: 16 characters point description; 16 characters zone description.
•
50 devices zones
•
CBE (Control-by event) equation for activations with logical operators (AND, OR, etc.).
•
100 logical Groups
•
Historical archive in non-volatile memory
•
Real time clock
•
Detector Line Auto-programming with the automatic identification of the connected devices type
•
Automatic identification of double address devices
•
Software algorithm for alarm and trouble criteria.
•
Automatic switch for day/night detectors sensitivity.
•
Warning indication of the detectors cleaning need
•
Warning indication of low sensitivity of the detectors
•
Programmable alarm threshold for the detectors
•
Software function programming defined for the various devices
•
Walk-Test functions selectable by zone