Troubleshooting - heat-timer MPCQ Platinum Installation And Operation Instructions For

Steam heating and sequencing control
Table of Contents

Advertisement

Sensor INPUTS
Display shows Sensor OPEN or SHORT
When OPEN, Check if the sensor is connected and the wires are continuous to the MPCQ Platinum. Finally, follow the procedure
for Display Shows Incorrect Temperature or Pressure. When in SHORT Remove the wires from the sensor terminals. The
display should change to read OPEN. If it does not, the MPCQ Platinum may be damaged.
Display shows an Incorrect Temperature
Remove the wires from the sensor terminals. The display should change to read OPEN. If it does not, the MPCQ Platinum may
be damaged. Take an ohm reading across the detached sensor wires. The ohm reading should correspond to the Temperature
sensor Table. If it does not, the sensor may be damaged.
Display shows an Incorrect Pressure
If the reading is a specified amount above or below the actual pressure adjust it using the System Trim. If the reading is SHORT,
remove the wires from the sensor terminals. The display should change to read OPEN. If it does not, the MPCQ Platinum may
be damaged.
CONTROL OPERATION
Too Much Heat
Check if the control has any of the following:
Heat Adjustment - If the overheating occurs only during specific hours, check the Day/Night
Schedule (page 26), Day/Night Heat Adjustment (page 21), Day/night Cutoff (page 21), or the
Setback settings (page 22).
Boiler Mode Settings - The MPCQ Platinum will only sequence boilers their mode is set to
Auto or Standby. Make sure none of the boilers have their Mode set to ON. See page 26.
Control Settings - The Last Stage Hold will allow only the Lead boiler to exceed the set point.
If the setting is too high and only the Lead boiler is on, the system can overshoot. Reduce the
Last Stage Hold setting. See page 24.
Too Little Heat
Check if the control has any of the following:
Setback and Day/Night Schedule - If reduced heat occurs only during specific hours, check
the Day/Night Schedule (page 26), Day/Night Heat Adjustment (page 21), Day/night Cutoff
(page 21), or the Setback settings (page 22).
Boiler Mode Settings - The MPCQ Platinum will only control boilers their mode is set to
Auto or Standby after a delay. Check if any boilers have their Mode set to Manual, Off, or
Standby Delay. See page 26.
Boilers are Short-Cycling
Minimum Runtime - Increase the Minimum Runtime only if all boilers tend to short-cycle.
See page 24.
Last Stage Hold - Increase the Last Stage Hold only if the lead boiler tends to short-cycle.
See page 24.
System is Overshooting or Oscillating
Reaction Time and Minimum Runtime - If the system is overshooting, increase the Reaction
Time (See page 23). This will allow the MPCQ Platinum enough time to respond before
bringing on another stage. However, if the system was oscillating, increase the Reaction Time
and the Minimum Runtime. See page 24.
PID vs OSS - If the application requires fast response that the normal PID mode cannot
provide, try using the OSS mode and adjust the Throttle according to the system requirements.
See page 17.
MPCQ Platinum Installation and Operation Manual

Troubleshooting

Temperature Sensor Chart
TEMPERATURE
Value
(in Degrees °F)
(in Ohms)
-30
117720
-20
82823
-10
59076
0
42683
10
31215
20
23089
25
19939
30
17264
35
14985
40
13040
45
11374
50
9944
55
8714
60
7653
70
5941
80
4649
90
3667
100
2914
110
2332
120
1879
130
1524
140
1243
150
1021
160
842
170
699
180
583
190
489
200
412
210
349
220
297
230
253
240
217
250
187