Troubleshooting - heat-timer Mini-Extension Installation And Operations

Sequencing modulating control for hydronic heating systems
Hide thumbs Also See for Mini-Extension:
Table of Contents

Advertisement

26
Heat-Timer Corp.
TEMPERATURE INPUTS
Display shows Sensor OPEN
Check the sensor is connected and the wires are continuous to the Mini-MOD. Finally follow
the procedure for Incorrect Temperature Display.
Display shows Sensor SHORT
The Mini-MOD sees a short across the input terminals. Remove the wires from either the
SYSTEM TEMP or OUT TEMP terminals (whichever is reading SHORT). The display should
change to read OPEN. If it doesn't, the Mini-MOD may be damaged.
Display shows an Incorrect Temperature Display
Remove the wires from either the SYSTEM TEMP or OUT TEMP terminals (whichever is
reading incorrectly). The display should change to read OPEN. If it doesn't, the Mini-MOD
may be damaged. Take an ohm reading across the detached sensor wires. The ohm reading
should correspond to the side chart. If it doesn't, the sensor may be damaged.
CONTROL OPERATION
No Heat
(Check Diagram on next page)
Too Much Heat
Check if the control has any of the following:
Domestic Hot Water call - The Mini-MOD will raise the temperature of the system to either
200˚F or Maximum Water Temperature on a DHW call, connected to terminals 29 and 30.
Check to see if there is a call for DHW and the length of time it lasts.
Reset Ratio and Offset - If excessive heat occurs only in certain weather, adjust the Reset
Ratio and Offset (See Understanding Operating Concept). If excessive heat occurs year round,
reduce the Offset.
Boiler Mode Settings - The Mini-MOD will only modulate boilers their mode is set to Auto
or Standby. Check to if any boiler stage is set to Manual or On.
Control Settings - The Last Stage Hold will allow only the Lead boiler to stay on for an
additional number of degrees. If the setting is too high, and only the Lead boiler is on, the
system can over heat. Reduce the Last Stage Hold setting.
Too Little Heat
Check if the control has any of the following:
Reset Ratio and Offset - If reduced heat occurs only in certain weather, adjust the Reset
Ratio and Offset (See Understanding Operating Concept). If reduced heat occurs year round,
increase the Offset.
Setback and Day/Night Schedule - If reduced heat occurs only during specific hours, check
the Day/Night Schedule and the Setback values. Either reduce the Setback setting or change
the Day and Night Schedules.
Boiler Mode Settings - The Mini-MOD will only modulate boilers their mode is set to Auto or Standby. Check if any boiler
stage is set to Manual, Off, or Standby.
Boilers are Short-Cycling
Lag Delay - Increase the Lag Delay only if all boilers tend to short-cycle.
Last Stage Hold - Increase the Last Stage Hold only if the lead boiler tends to short-cycle.
System is Overshooting or Undershooting
Gain - If the system is overshooting reduce the Gain.
Gain - If the system is undershooting increase the Gain.

TROUBLESHOOTING

Temperature Sensor Chart
TEMPERATURE
Value
(in Degrees °F)
(in Ohms)
-30
117720
-20
82823
-10
59076
0
42683
10
31215
20
23089
25
19939
30
17264
35
14985
40
13040
45
11374
50
9944
55
8714
60
7653
70
5941
80
4649
90
3667
100
2914
110
2332
120
1879
130
1524
140
1243
150
1021
160
842
170
699
180
583
190
489
200
412
210
349
220
297
230
253
240
217
250
187