Inhibit Level Selection

Use the inhibit switch to set the level of current which is required when
inhibit is active.
1) With this switch in the upper position, a current of 4 mA is output in inhibit
2) With this switch in the lower position, a current of 2 mA is output in inhibit

Current Source/Sink Selection

Use the current source/sink switch to choose between source mode and
sink mode.
1) Detector sink mode: With this switch in the upper position, the analog
2) Detector source mode: With this switch in the lower position, the analog
All manuals and user guides at all-guides.com
mode. In the case of oxygen versions only, 17.4 mA is used.
mode on all versions.
output drives current through the controller sensing circuit.
output draws current through the controller sensing circuit.
NOTE
The load resistance of the controller must be between 33 Ω and
250 Ω. When the mA output is not being used, a 33 Ω, 0.125 W load
resistor should be connected between terminal 3 (4–20 mA) and
terminal 2 (0 V) for source mode or terminal 1 (+24 V DC) for sink
mode. Failure to do so will cause the unit to enter a fault condition.