ELECTRICAL WIRING
ELB
Total indoor
unit capacity
(n/A/mA)
*9
< 7A
2/40/30
<10A
2/40/30
< 15A
2/40/30
ELB: Earth Leakage Breaker; CB: Circuit Breaker
N O T E
17.3 WIRING CONNECTION
1 The wiring connection for the indoor unit is shown below.
Power source cable
Terminal block (black)
Wire clamp
Control cable /
Remote control cable
Earth screw
Wire clamp
Terminal block (white)
PCB
N O T E
31
PMML0416A rev.0 - 12/2015 - P5415720
Power Source
Main Switch
CB (fuse)
Switch
capacity (A)
capacity (A)
*9
*10
30
15
30
20
30
30
Minimum
Wiring
wire size
length (m)*1)
2
(mm
)
*11
2.5
30
4.0
34
6.0
34
2 When installing the optional air panel, connect the connector
for the auto swing motor and the connector for the indoor
unit. Refer to the technical documentation of the optional air
panel for details.
Hinge
Air panel
(Indoor unit)
N O T E
Transition
Earth wire
wire size for
size (mm
2
)
control circuit
2
*12
(mm
)
*13
2.5
2 Core cable
(Shielded twist
4.0
pair cable)
6.0
0.75 ~ 1.25
Wiring connector for louver
(Air panel side)
Connector (CN17)
(Indoor unit PCB)
Remote
control
switch cable
(mm
2
)
2 core twist
pair cable
0.75