INDOOR UNIT INSTALLATION
14.2.2
D A N G E R
down and it may lead to injuries.
Select the installation location as follows:
(A) Minimum Space
(B) Down Slope Pitch of Drain Pipe: 1/25 to 1/100
The sensing area for the motion sensor is shown in the
with the air panel.
Installation Height of Indoor Unit: h (m)
Sensing Area for Motion Sensor: øa (m)
Motion Detection
Motion sensor
17
PMML0416A rev.0 - 12/2015 - P5415720
Min. 10mm
Clearance
345mm
Unit Height in
false ceiling
Drain piping
Down Slope Pitch:
1/25 to 1/100
3.1
Human Motion
h
φa
Consider the air distribution from the indoor unit to the space
of the room, and select a suitable location so that uniform air
temperature in the room can be obtained.
the indoor unit.
Install the unit where there is no obstacles which may
hamper the suction air and discharged air.
Do not install the unit near a door or a window where the
indoor unit may contact humid outside air. Otherwise, dew
condensation may occur.
dew condensation.
If installing the indoor unit to a high ceiling, the warmed air
may stay around the ceiling during heating operation. Thus,
the parallel installing of a circulator is recommended.
outlet blows directly to the temperature detecting devices
such an alarm device or a control device. It may cause a
failure of an alarm device or a control device.
For simultaneous operation of multiple units (twin, triple and
quad combination) , the units must be installed in the same
room and be operated under the same conditions. If the
room is partitioned by a wall, furniture or a curtain, etc., it
may cause an operation failure. Take care when rearranging
furniture or remodeling the room after installation as well.