INDOOR UNIT INSTALLATION
14.2 INITIAL CHECK
D A N G E R
The refrigerant R410A, charged in the HITACHI air conditioners and
heat pumps, is an incombustible and non-toxic gas. However, if
maximum permissible concentration of R410A in air is 0.42 kg/m
according to ISO5149. Therefore, some effective measure must be
taken to lower the R410A concentration in air below 0.42 kg/m
case of leakage.
Calculation of Refrigerant Concentration
1 Calculate the total quantity of refrigerant R (kg) charged in
the system connecting all the indoor units of rooms to be
air-conditioned.
2 Calculate the room Volume V (m
3 Calculate the refrigerant concentration C (kg/m
according to the following equation.
R: Total quantity of charged refrigerant (kg)
V: Room volume (m
Refer to the the technical documentation of outdoor unit for
details.
Make sure that the refrigerant leakage test should be
performed. The refrigerant (Fluorocarbon R410A) for this
unit is incombustible, non-toxic and odorless. However if
suffocation.
C A U T I O N
N O T E
a
c
d
e
16
PMML0416A rev.0 - 12/2015 - P5415720
3
) of each room.
3
) of the room
C: Refrigerant
=
concentration
3
)
3
for R410A
14.2.1
operation and maintenance as shown below.
3
,
the indoor unit.
When equipping the duct adapter (optional), set up a service
3
, in
access door at the duct adapter side in order to install the
duct adapter. Refer to the installation manual of the duct
adapter for details.
Min.
100
Min.
100
Min.
100
Min. 100
Min. 1500
Min. 1000
Single unit installation
(mm)
Service
access panel
Min.
500
Piping
connection
side
Multiple unit installation
Service
access panel
Min.
500
Service
access panel
Min.
500
Piping
connection side
Min. 1500
(Piping connection side)
(Piping Connection Side)
Min. 500
Min.
1000