March 2022
Figure 5-2: Typical Settings for High Level Applications
A. Mode "Dry On" and 1 second time delay
The "Wet On" mode is recommended for low level alarm installations
5-3).
Figure 5-3: Typical Settings for Low Level Applications
A. Mode "Wet On" and 1 second time delay
5.1.1
Set the mode switch and switching time delay
Procedure
1. Select "Dry on" or "Wet on" mode.
2. Select 0.3, 1, 3, 10, or 30 seconds for the delay before switching
output state.
Note
There is a five second delay before changes to the mode and time
delay become active.
Quick Start Guide
A
Dry On
Wet On
0.3
0.3
1
1
3
3
10
10
30
30
Seconds Delay
A
Dry On
Wet On
0.3
0.3
1
1
3
3
10
10
30
30
Seconds Delay