PXL Conventional Fire Alarm Control Panel
AUTOMATIC BATTERY DISCONNECT
Canadian systems require automatic battery disconnect. In order to select this option, set
Switch 5 on S1 of the PPS-10M to the ON position. Connect the battery to the PPS-10M
through the supervisory relay.
• Connect the NO contact to Battery+ terminal and Common to Bat+ terminal of the PPS-10M.
• Connect Battery- terminal to Bat- of the PPS-10M.
• If a supervisory relay is required, use a PRM-4 and configure the relay as a global supervisory.
68
Technical Manuals Online! - http://www.tech-man.com
PPS-10M Wiring for Canadian Automatic Battery Disconnect
firealarmresources.com
Figure 25