PXL Conventional Fire Alarm Control Panel
Technical Manuals Online! - http://www.tech-man.com
APPENDIX B
Module Power Calculations
and
Electrical Requirements for
Battery Calculations
MODULE POWER CALCULATIONS
Module Type
PCM-1 Module
0.093A
PZE-4B Module(s)
Number of modules
________ x 0.031A =
PNC-2Z Module(s)
Number of modules
________ x 0.036A =
PRM-4 Module(s)
Number of modules
________ x 0.060A
LED-3/4 Module(s)
Number of modules
________ x 0.042A
RSA Module(s)
RSA-16R / RSA-16B = 220ma
RSA-16RTL / RSA-16BTL = 450mA
RSA-16RSC / RSA-16BSC = 450mA
Number of modules
________ x ________A =
4 IDC Zones in Alarm
0.720A
Total Current
(Must be 1.8A or less per PPS-10M power supply)
firealarmresources.com
Appendix B
+24 VDC
Regulated Current
0.093A
______A
______A
______A
______A
______A
0.720A
______A
65