Download Print this page

Siemens CERBERUS PYROTRONICS PXL Installation, Operation And Maintenance Manual page 64

Conventional fire alarm control panel

Advertisement

PXL Conventional Fire Alarm Control Panel
Trouble Message Text
PRM MOD X NO RESPONSE
PRM MOD X NOT SPEC'D
PRM MOD X WATCHDOG
PZE MOD X MULTI/UNKN
PZE MOD X NOT SPEC'D
PZE MOD X WATCHDOG
PZE NEEDS NEW
FIRMWARE
RELAY XX BYPASSED
RSA MOD X MULTI/UNKN
RSA MOD X NO RESPONSE
RSA MOD X NOT SPEC'D
SYSTEM WATCHDOG
ZONE X COMM ERR
ZONE XX
ZONE XX BYPASSED
ZONE XX NO RESPONSE
*Modules purposely removed from the system may be removed from the configuration using
the "Delete Module Option" in the Program menu.
X = Module number
58
Technical Manuals Online! - http://www.tech-man.com
TROUBLE MESSAGES (Cont.)
Condition
PRM not responding
PRM responding but not in
configuration
PRM module watchdog
PZE not responding and ASC
routine will not run
PZE responding but not in
configuration
PZE module watchdog
Firmware error for CANADA
country selection occurs during
reset
Relay bypassed
RSA not responding and ASC
routine will not run
RSA not responding
RSA responding but not in
configuration
System watchdog
PCM/PZE communication error
IDC zone trouble
IDC zone bypassed
PCM/PZE not responding
firealarmresources.com
Testing and Troubleshooting
Possible Cause
• Module removed from system*
• Module failed
• Module address changed
• PRM module added but system
not reconfigured
• PRM module address changed
Module locked up; reset the panel
Two or more PZEs installed with same
dipswitch address
• PZE module added but system
not reconfigured
• PZE module address changed
Module locked up; reset the panel
PCM-1 and/or PZE-4B module has Rev.
1.0 firmware. Upgrade to Rev. 3.x or
higher
Relay bypassed
Two or more RSAs installed with same
dipswitch address
• Module removed from system*
• Module failed
• Module address changed
• RSA module added but system
not reconfigured
• RSA module address changed
Panel locked up; reset the panel
• Data transmission failure
• Module failed
IDC zone open
IDC zone bypassed
• Module removed from system*
• Module failed
• Module address changed

Advertisement