Siemens CERBERUS PYROTRONICS PXL Installation, Operation And Maintenance Manual page 62

Conventional fire alarm control panel

Advertisement

PXL Conventional Fire Alarm Control Panel
Trouble Message Text
AC POWER FAULT
BELL XX
BELL XX BYPASSED
GROUND FAULT
INCORRECT PZE PIC
LED MOD X MULTI/UNKN
LED-3/4 MOD X NO
RESPONSE
LED-3/4 MOD X NOT SPEC'D
MULTI RESP LED-3/4 MOD X
MULTI RESP PCM MOD O
MULTI RESP PNC MOD X
MULTI RESP PPS MOD X
MULTI RESP PRM MOD X
MULTI RESP PZE MOD X
MULTI RESP RSA MOD X
* Modules purposely removed from the system may be removed from the configuration using
the "Delete Module Option" in the Program menu.
X = Module number
56
Technical Manuals Online! - http://www.tech-man.com
TROUBLE MESSAGES
Condition
System powers up normally but
nothing shows on LCD display
AC power off/low
NAC trouble
NAC bypassed
Ground fault
Firmware error for CANADA
country selection
LED-3/4 not responding and ASC
routine will not run
LED-3/4 not responding
LED-3/4 responding but not in
configuration
Multiple Response at LED-3/4
address
Multiple Response at PCM
address
Multiple Response at PNC
address
Multiple Response at PPS
address
Multiple Response at PRM
address
Multiple Response at PZE
address
Multiple Response at RSA
address
firealarmresources.com
Testing and Troubleshooting
Possible Cause
Contrast not adjusted properly
• Loss of AC mains
• AC brownout
• Blown secondary fuse
• Open transformer primary/secondary
NAC open
NAC shorted
NAC bypassed
• +24 shorted to earth ground
• -V shorted to earth ground
• F+, R+, R-, F- of an NAC shorted
to earth ground
• IDC+ or IDC- of an IDC zone
shorted to earth ground
PCM-1 and/or PZE-4B module has Rev. 1.0
firmware. Upgrade to Rev. 3.x or higher
Two or more LED-3/4s installed with same
dipswitch address
• Module removed from system*
• Module failed
• Module address changed
• LED module added but system not
reconfigured
• LED module address changed
• Two LED modules set to same address
• LED set to address out of range
Module failed
• Two PNC modules set to same address
• PNC set to address out of range
• Two PPS modules set to same address
• PPS set to address out of range
• Two PRM modules set to same address
• PRM set to address out of range
• Two PZE modules set to same address
• PZE set to address out of range
• Two RSA modules set to same address
• RSA set to address out of range