Siemens CERBERUS PYROTRONICS PXL Installation, Operation And Maintenance Manual page 32

Conventional fire alarm control panel

Advertisement

PXL Conventional Fire Alarm Control Panel
26
Technical Manuals Online! - http://www.tech-man.com
STEP 13—Check Field Wiring
Field Wiring Checkout Procedure
STEP 14—Install Field Wiring
Wiring to the PSE-1 Enclosure
observed
The fire alarm power-limited circuits are installed using
Types FPL, FPLR, FPLP or permitted substitute cable,
provided these power-limited cable conductors extending
beyond the jacket are separated by a minimum of 0.25 in.
(6.35 mm) or by a nonconductive sleeve or nonconductive
barrier from all other conductors.
NOTE:
firealarmresources.com
Installation
must be