PXL Conventional Fire Alarm Control Panel
12
Technical Manuals Online! - http://www.tech-man.com
STEP 4Install the Optional PRM-4
The PPS-10M Power Supply module must be installed before
mounting and wiring the PRM-4 Relay module.
SETTING THE ADDRESS ON THE PRM-4
Module
Number
1
2
3
4
5
6
7
8
X = SWITCH CLOSED OR ON, O = SWITCH OPEN OR OFF
firealarmresources.com
TABLE 2
Relay
Switch Setting
Range
1
2
3
4
1-4
X
O
O
O
5-8
O
X
O
O
9-12
X
X
O
O
13-16
O
O
X
O
17-20
X
O
X
O
21-24
O
X
X
O
25-28
X
X
X
O
29-32
O
O
O
X
Figure 7
PRM-4 Module Board
Installation
5
O
O
O
O
O
O
O
O