PXL Conventional Fire Alarm Control Panel
ELECTRICAL REQUIREMENTS FOR BATTERY CALCULATIONS
PCM-1 Module
PPS-10M Module
PZE-4B Module(s)
Number of modules x current
________ x 0.039A =
PNC-2Z Module(s)
Number of modules x current
________ x 0.012A =
PRM-4 Module(s)
Number of modules x current
________ x 0.007A (Standby) =
________ x 0.067A (Alarm) =
IDC Current:
Alarm Current = .180/zone
4 x .180 = 0.72A
NAC/Aux Port Current:
Aux
________
NAC 1
________
NAC 2
________
NAC 3
________
NAC 4
________
NAC 5
________
NAC 6
________
NAC 7
________
NAC 8
________
NAC 9
________
NAC 10
________
NAC 11
________
NAC 12
________
NAC 13
________
NAC 14
________
NAC 15
________
NAC 16
________
LED-3/4 Module(s)
Number of modules
________ x 0.009A (Standby) =
________ x 0.042A (Alarm) =
RSA Module(s)
Number of modules
________ x 0.02A (Standby) =
________ x 0.02A + 0.013 per LED (Alarm) =
Total Standby Current
___________
Total Alarm Current
___________
_________ x 1.35 = Minimum A-H Battery Size
<= means less than or equal to
66
Technical Manuals Online! - http://www.tech-man.com
Standby Current 0.039A
Alarm Current 0.039A
Standby Current 0.012A
Alarm Current 0.012A
Standby Current 0.007A
Alarm Current 0.067A
Current <=2.0A per NAC
<=1.0A Aux
(Max 10A)
Total
Standby Hours (24, 48, or 60)
x
__________________
A-H Multiplier Factor (5 Min.)
x
0.084
Total A-H
Total A-H x Batterycharging Factor
firealarmresources.com
Standby
Alarm
Current
Current
0.147A
0.147A
0.088A
0.118A
______A
______A
______A
______A
______A
______A
0A
0.72A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
0A
______A
______A
______A
______A
______A
______A
______A
Standby A-H Current
=
______________A-H
Alarm A-H Current
=
______________A-H
______________A-H
_________________
Appendix B
NOTES: