Installing The Heating And Domestic Hot Water Circuit; Installing The Electrical Connections - Vaillant aroTHERM VWL Series Manual

Refrigerant-split heat pump system
Hide thumbs Also See for aroTHERM VWL Series:
Table of Contents

Advertisement

Work step
10
Outdoor unit
► Evacuating the refrigerant circuit
11
Outdoor unit
► Adding additional refrigerant
12
Outdoor unit
► Releasing the refrigerant
3.4

Installing the heating and domestic hot water circuit

→ uniTOWER installation and maintenance instructions, from section 5.1 onwards
→ Accessory set-up instructions
Work step
13
Indoor unit
► Installing the domestic hot and cold water
connection
► Installing heating circuit connections
14
Heating circuit
► Connecting the buffer cylinder
► Connecting the bypass valve
15
Heating circuit
► Connecting the additional expansion vessel
16
DHW circuit
► Connecting the expansion vessel
17
Safety devices
► Installing the safety devices
3.5

Installing the electrical connections

→ aroTHERM installation and maintenance instructions, from section 6.1 onwards
→ uniTOWER installation and maintenance instructions, from section 6.1 onwards
→ multiMATIC installation instructions, from section 4.1 onwards
→ Accessory set-up instructions
Work step
18
Outdoor temperature sensor
► Connecting the outdoor temperature sensor
19
Outdoor unit
► Establishing the power supply
20
Indoor unit
► Establishing the power supply
21
Indoor unit, electrical house installation
► Installing components for the energy supply
company lockout function
0020243831_00 System assistant
System without system control (0020253231) 3
Selected information/measures
► Drain the nitrogen that was poured in.
► Connect a vacuum pump.
► Drain the refrigerant circuit in two rounds of 30 minutes each.
► After each round, check whether the pressure is stable:
0.1 kPa (1.0 mbar) absolute pressure
Condition: Basic length of the refrigerant pipe > 15 m
► For each additional metre (above 15 m), add additional refrigerant:
30 g/m for an output of up to 5 kW
70 g/m for an output of 7 kW or higher
► Turn the isolation valves as far as they will go.
Selected information/measures
► Observe the connection symbols.
→ uniTOWER installation and maintenance instructions, section 3.7
Condition: The dimension of the installed expansion vessel is not sufficient
► Ensure that there is sufficient dimensioning.
► If required, adjust the pre-charge pressure.
► Ensure that all of the required safety device have been installed in the sys-
tem.
Selected information/measures
► Select a correct cable cross-section.
► Comply with the connection conditions for the energy supply company.
► Determine whether an electrical connection 1~/230 V or 3~/400 V (→ data
plate) is required.
► Determine whether the power supply should be set up using a single-tariff
meter or a dual-tariff meter.
Condition: Depending on the installation site
► Install one or two type-B residual-current circuit breakers for the outdoor unit,
depending on the connection type.
► Route the cables from the rear into the product and, from there, to the front
through the strain relief.
Condition: Depending on the installation site
► Install a type-A or type-B residual-current circuit breaker for the indoor unit.
Condition: Power supply via a dual-tariff meter
Option 1: Disconnect the power supply with contactor
Option 2: Actuating the ESC contact
→ uniTOWER installation and maintenance instructions, section 6.4
9

Advertisement