DEMAND LIMIT (CCN Loadshed Controlled) — To con-
figure Demand Limit for CCN Loadshed control set the De-
mand Limit Select (Configuration
Then configure the Loadshed Group Number (Configura-
tion
RSET
SHNM), Loadshed Demand Delta (Configu-
ration
RSET
SHDL), and Maximum Loadshed Time
(Configuration
RSET
SHTM). See Table 27.
The Loadshed Group number is established by the CCN
system designer. The ComfortLink™ controls will respond to a
Redline command from the Loadshed control. When the
Redline command is received, the current stage of capacity is
set to the maximum stages available. Should the loadshed con-
trol send a Loadshed command, the ComfortLink controls will
reduce the current stages by the value entered for Loadshed
Demand delta. The Maximum Loadshed Time is the maximum
100
80
60
100% CAPACITY AT 4 mA
40
20
0
0
100
(38)
90
(32)
80
(27)
70
(21)
60
(15)
50
(10)
40
(4.4)
30
(-1)
20
(-7)
10
(-12)
0
(-17)
4
EMM — Energy Management Module
RSET
DMDC) to 3.
75% CAPACITY AT 12 mA
2
6
4
DEMAND LIMIT SIGNAL – 4 - 20 mA INPUT
Fig. 18 — 4 to 20-mA Demand Limiting
(FLUD = 2) MINIMUM
SET POINT 14 F (-10 C)
6.3
8.6
Fig. 19 — Cooling Set Point (4 to 20 mA)
length of time that a loadshed condition is allowed to exist. The
control will disable the Redline/Loadshed command if no
Cancel command has been received within the configured
maximum loadshed time limit.
Cooling Set Point (4 to 20 mA) —
and generated, externally powered 4 to 20 mA signal can be
used to provide the leaving fluid temperature set point. Connect
the signal to LVT-10,8 (+,–). See Table 27 for instructions to
enable the function. Figure 19 shows how the 4 to 20 mA sig-
nal is linearly calculated on an overall 10 F to 80 F range for
fluid types (Configuration
point will be limited by the fluid (FLUD) type. Be sure that the
chilled water loop is protected at the lowest temperature.
8
12
10
14
(FLUD = 1) MINIMUM
SET POINT 38 F (3.3 C)
10.9
13.1
4 TO 20 mA SIGNAL TO EMM
32
A field supplied
OPT1
FLUD) 1 or 2. The set
50% CAPACITY AT 20 mA
16
18
20
MAXIMUM
SET POINT
70 F (21.1 C)
15.4
17.7
20