provided in the EconoMi$er IV wiring harness. (See Fig.
70.)
ECONOMI$ERIV
Fig. 79 - - Return Air Temperature or Enthalpy Sensor
Mounting Location
ECONOMI$ERIV
CONTROLLER
GROMMET
RETURN AIR
SENSOR
RETURN DUCT
(FIELD-PROVIDED)
C07085
CONTROL
CONTROL POINT
CURVE
APPROX. deg. F (deg. C)
AT 50% RH
A
73 (23)
B
70 (21)
C
67 (19)
D
63 (17)
(18)
60
(16)
A
55
(13)
B
50
C
(10)
45
D
(7)
40
(4)
35
(2)
35
40
45
50
55
60
(2)
(4)
(7)
(10)
(13)
(16)
APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)
Fig. 80 - - Enthalpy Changeover Setpoints
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower
temperature airstream is used for cooling. When using this
mode of changeover control, turn the enthalpy setpoint
potentiometer fully clockwise to the D setting. (See Fig.
76.)
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part
number HH57AC078) is required. Replace the standard
outdoor dry bulb temperature sensor with the accessory
enthalpy sensor in the same mounting location. (See Fig.
79.) When the outdoor air enthalpy rises above the
outdoor enthalpy changeover setpoint, the outdoor-air
damper moves to its minimum position. The outdoor
enthalpy changeover setpoint is set with the outdoor
enthalpy setpoint potentiometer on the EconoMi$er IV
controller. The setpoints are A, B, C, and D. (See Fig. 80.)
The factory-installed 620-ohm jumper must be in place
across terminals S
controller.
85
90
95
100
105
(29)
(32)
(35)
(38)
(41)
80
(27)
75
(24)
70
(21)
65
A
B
C
D
65
70
75
80
85
90
95
100
105
(18)
(21)
(24)
(27)
(29)
(32)
(35)
(38)
(41)
59
and SR+ on the EconoMi$er IV
R
110
(43)
HIGH LIMIT
CURVE
110
(43)
C06037