Fuel Types and Pressures
Natural Gas — The 48TC unit is factory- - equipped for use
with Natural Gas fuel at elevation under 2000 ft (610 m).
See section Orifice Replacement for information in
modifying this unit for installation at elevations above
2000 ft (610 m).
Gas line pressure entering the unit's main gas valve must
be within specified ranges. Adjust unit gas regulator valve
as required or consult local gas utility.
Table 4 – Natural Gas Supply Line Pressure Ranges
UNIT MODEL
UNIT SIZE
48TC
All
Manifold pressure is factory- - adjusted for NG fuel use.
Adjust as required to obtain best flame characteristic.
Table 5 – Natural Gas Manifold Pressure Ranges
UNIT
UNIT
HIGH
MODEL
SIZE
FIRE
48TCD,S
3.5 in. wg
48TCE,R
All
(872 Pa)
48TCF,T
48TCL
3.5 in. wg
48TCM
All
(872 Pa)
48TCN
NA: Not Available
{ 3 Phase models only
Liquid Propane — Accessory packages are available for
field- - installation that will convert the 48TC unit (except
low NO
model) to operate with Liquid Propane (LP)
x
fuels. These kits include new orifice spuds, new springs
for gas valves and a supply line low pressure switch. See
section on Orifice Replacement for details on orifice size
selections.
Low NO
models include specially- - sized orifices and use
x
of different flue flow limits and tube baffles. Because of
these extra features, conversion of these models to LP is
not recommended.
Fuel line pressure entering unit gas valve must remain
within specified range.
Limit Switch
and Shield
C08284
MIN
MAX
4.0 in. wg
13.0 in. wg
(996 Pa)
(3240 Pa)
LOW
RANGE
FIRE
1.7 in. wg
2.0--- 5.0 in. wg (Hi)
(423 Pa){
(498--- 1245 Pa)
2.0--- 5.0 in. wg (Hi)
NA
(498--- 1245 Pa)
Table 6 – Liquid Propane Supply Line Pressure Ranges
UNIT MODEL
UNIT SIZE
48TCD,E,F
All
48TCS,R,T
48TCL,M,N
All
Manifold pressure for LP fuel use must be adjusted to
specified range. Follow instructions in the accessory kit to
make initial readjustment.
Table 7 – Liquid Propane Manifold Pressure Ranges
UNIT MODEL
UNIT SIZE
48TCD,S
48TCE,R
All
48TCF,T
48TCL,
48TCM,
All
48TCN
NA: Not Available
{ 3 Phase models only
Supply Pressure Switch — The LP conversion kit includes
a supply low pressure switch. The switch contacts (from
terminal C to terminal NO) will open the gas valve power
whenever the supply line pressure drops below the
setpoint. See Fig. 29 and Fig. 30. If the low pressure
remains open for 15 minutes during a call for heat, the
IGC circuit will initiate a Ignition Fault (5 flashes)
lockout. Reset of the low pressure switch is automatic on
rise in supply line pressure. Reset of the IGC requires a
recycle of unit power after the low pressure switch has
closed.
Fig. 29 - - LP Low Pressure Switch (Installed)
IGC
BRN
C
J2-11
IGC
J2-12
TSTAT
W2
PNK
Fig. 30 - - LP Supply Line Low Pressure Switch Wiring
23
MIN
MAX
11.0 in. wg
13.0 in. wg
(2740 Pa)
(3240 Pa)
NA
NA
HIGH FIRE
LOW FIRE
10.0 in. wg
5.0 in. wg
(2490 Pa)
(1245 Pa){
NA
NA
C08238
LP LPS
BRN
NO
C
MGV
GRA
C08285