Carrier 48TCA04---A12 Service And Maintenance Instructions page 36

Nominal 3 to 10 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

Table 15 – Thermistor Resistance vs Temperature
Values for Space Temperature Sensor, Supply Air
Temperature Sensor, and Outdoor Air Temperature
Sensor
TEMP
TEMP
(C)
---40
---35
---30
---25
---20
---15
---10
---5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
NOTE: The sensor must be mounted in the discharge
airstream downstream of the cooling coil and any heating
devices. Be sure the probe tip does not come in contact
with any of the unit's heater surfaces.
Outdoor Air Temperature (OAT) Sensor — The OAT is
factory- - mounted in the EconoMi$er 2 (FIOP or
accessory). It is a nominal 10k ohm thermistor attached to
an
eyelet
mounting
temperature- - resistance characteristic.
EconoMi$er 2 — The PremierLink control is used with
EconoMi$er 2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the PremierLink control; EconoMi$er 2 has no internal
logic device.
Outdoor air management functions can be enhanced with
field- - installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
sensor
2
Outdoor air CO
sensor
2
Refer to Table 16 for accessory part numbers.
RESISTANCE
(F)
(Ohms)
---40
335,651
---31
242,195
---22
176,683
---13
130,243
---4
96,974
5
72,895
14
55,298
23
42,315
32
32,651
41
25,395
50
19,903
59
15,714
68
12,494
77
10,000
86
8,056
95
6,530
104
5,325
113
4,367
122
3,601
131
2,985
140
2,487
149
2,082
158
1,752
ring.
See
Table
15
Field connections — Field connections for accessory
sensor and input devices are made at the 16- - pole terminal
block (TB1) located on the control box bottom shelf in
front of the PremierLink control. Some input devices also
require a 24- - vac signal source; connect at LCTB terminal
R at "THERMOSTAT" connection strip for this signal
source. See connections figures on following pages for
field connection locations (and for continued connections
at the PremierLink board inputs).
Table 17 provides a summary of field connections for
units equipped with Space Sensor. Table 18 provides a
summary of field connections for units equipped with
Space Thermostat.
Space
Sensors
factory- - shipped configured for Space Sensor Mode. A
Carrier T- - 55 or T- - 56 space sensor must be used. T- - 55
space temperature sensor provides a signal of space
temperature to the PremierLink control T- - 56 provides
same space temperature signal plus it allows for
adjustment of space temperature setpoints from the face of
the sensor by the occupants. See Table 15 for temperature
versus resistance characteristic on the space sensors.
Connect T- - 55 - - See Fig. 43 for typical T- - 55 internal
connections. Connect the T- - 55 SEN terminals to TB1
terminals 1 and 3 (see Fig. 44).
1
2
SW1
for
Fig. 43 - - T- - 55 Space Temperature Sensor Wiring
SEN
SEN
Fig. 44 - - PremierLink T- - 55 Sensor
36
- -
The
PremierLink
controller
3
4
5
6
RED(+)
WHT(GND)
CCN COM
BLK(-)
SEN
BRN (GND)
SENSOR WIRING
BLU (SPT)
TB1
1
3
is
C08201
PL
J6-7
J6-6
C08212