Carrier 48TCA04---A12 Service And Maintenance Instructions page 33

Nominal 3 to 10 tons with puron (r-410a) refrigerant
Table of Contents

Advertisement

LED
FLASH
DESCRIPTION
CODE
On
Normal Operation
Off
Hardware Failure
2
Limit Switch Fault
Flashes
3
Flame Sense Fault
Flashes
4
Four Consecutive Limit
Flashes
Switch Fault
5
Ignition Fault
Flashes
6
Induced Draft Motor
Flashes
Fault
7
Rollout Switch Lockout
Flashes
8
Internal Control Lockout
Flashes
9
Temporary Software
Flashes
Lockout
LEGEND
IGC --- Integrated Gas Unit Control
LED --- Light--- Emitting Diode
NOTES:
1. There is a 3--- second pause between alarm code displays.
2. If more than one alarm code exists, all applicable alarm codes will be displayed in numerical sequence.
3. Alarm codes on the IGC will be lost if power to the unit is interrupted.
Table 14 – IGC Board LED Alarm Codes
ACTION TAKEN BY
RESET METHOD
CONTROL
No gas heating.
Gas valve and igniter
Off.
Limit switch closed,
Indoor fan and inducer
or heat call (W) Off.
On.
Flame sense normal.
Indoor fan and inducer
Power reset for LED
On.
reset.
Heat call (W) Off.
No gas heating.
Power reset for LED
reset.
Heat call (W) Off.
No gas heating.
Power reset for LED
reset.
If heat off: no gas
Inducer sense nor-
heating.
mal, or heat call (W)
If heat on: gas valve
Off.
Off and inducer On.
Gas valve and igniter
Off.
Power reset.
Indoor fan and inducer
On.
No gas heating.
Power reset.
1 hour auto reset, or
No gas heating.
power reset.
Loss of power to the IGC. Check 5 amp
fuse on IGC, power to unit, 24V circuit
breaker, transformer, and wiring to the
IGC.
High temperature limit switch is open.
Check the operation of the indoor (evapo-
rator) fan motor.
Ensure that the supply-air temperature
rise is within the range on the unit name-
plate. Check wiring and limit switch opera-
tion.
The IGC sensed a flame when the gas
valve should be closed. Check wiring,
flame sensor, and gas valve operation.
4 consecutive limit switch faults within a
single call for heat. See Limit Switch Fault.
Unit unsuccessfully attempted ignition for
15 minutes. Check igniter and flame sen-
sor electrode spacing, gaps, etc. Check
flame sense and igniter wiring. Check gas
valve operation and gas supply. Check
gas valve connections to IGC terminals.
BRN lead must be on Pin 11.
Inducer sense On when heat call Off, or
inducer sense Off when heat call On.
Check wiring, voltage, and operation of
IGC motor. Check speed sensor wiring to
IGC.
Rollout switch has opened. Check gas
valve operation. Check induced-draft
blower wheel is properly secured to motor
shaft.
IGC has sensed internal hardware or soft-
ware error. If fault is not cleared by reset-
ting 24 v power, replace the IGC.
Electrical interference is disrupting the
IGC software.
33
PROBABLE CAUSE