PEAK COMMUNICATIONS P7001R Installation And Operating Handbook page 25

Table of Contents

Advertisement

Ethernet Configure Message
This message is sent to the unit, when the host computer wishes to change the Ethernet settings of the
unit, subject to the fitting on the Ethernet option. The unit does not need to be in remote mode for this to
be achieved.
The layout of the configure message follows that of the status reply shown above.
Instruction 6, Subinstruction 1 (Ethernet Reconfiguration Request):
Message
Byte No.
1
2
3
4
5
6
7
8
23
24
39
40
55
56
57
58
73
74
When changing IP address or DHCP the unit will have to restart, it may take a few seconds for you to be
able to communicate with it again.
Page 25
Set Value /
(example)
02
7
?
6
'1'
'0'
'_'
"192.168.000.025"
'_'
"255.255.255.0"
'_'
"192.168.000.010"
'_'
'0'
'_'
"192.168.000.032"
?
03
P7001R & P7002R Series Converters
Length
Description
(bytes)
1
STX
1
No of bytes in message
1
Address
1
Message instruction
1
Ethernet Message sub instruction
1
DHCP
(0 = Disabled)
(1 = Enabled)
1
Separator character
15
Ipv4 address
1
Separator character
15
Subnet mask
1
Separator character
15
Gateway address
1
Separator character
1
SNMP
(0 = Disabled)
(1 = Enabled)
1
Separator character
15
SNMP trap address
1
Checksum
1
ETX

Advertisement

Table of Contents
loading

This manual is also suitable for:

P7002r

Table of Contents