Connecting Power; Connecting Ac Power - Siemens SIMATIC NET Installation Manual

Rugged ethernet switches
Hide thumbs Also See for SIMATIC NET:
Table of Contents

Advertisement

Installing the Device
2.6 Connecting Power
2.6

Connecting Power

The RP100 supports a single high AC, high DC or low DC power supply.
Note
2.6.1

Connecting AC Power

To connect a high AC power supply to the device, do the following:
Electrical hazard – risk of damage to equipment
Before testing the dielectric strength (HIPOT) in the field, remove the braided
ground cable connected to the surge ground terminal and chassis ground. This cable
connects transient suppression circuitry to chassis ground and must be removed in
order to avoid damage to transient suppression circuitry during testing.
10
For 100-240 VAC rated equipment, an appropriately rated AC circuit breaker
must be installed.
For 125-250 VDC rated equipment, an appropriately rated DC circuit breaker
must be installed.
Use minimum #16 gage copper wiring when connecting terminal blocks.
A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.
It is recommended to provide a separate circuit breaker for each power supply
module.
Equipment must be installed according to applicable local wiring codes and
standards.
NOTICE
RUGGEDCOM RP100
Installation Manual, 01/2021, C79000-G8976-1011-05