Arming Devices; Description; Command Centers; Assigning The Command Center An Address - Radionics D9000 Series Operation And Installation Manual

Control/communicator
Table of Contents

Advertisement

Description

Command Centers, maintained or momentary
contact keyswitches, or a combination of the two
are used to arm and disarm areas. The panel
may contain up to 8 areas. See the Introduction
section for a description of areas.

Command Centers

Terminals
The Radionics Command Center is a 4-wire
powered device used to arm and disarm areas,
annunciate complete system status, initiate
system tests, and control many functions of the
security system.
The system can supervise up to eight Command
Centers. The panel transmits a serial device
trouble report, SDI FAILURE in the Modem IIIa
format or TROUBLE ZN D in the BFSK format, if it
loses communication with a supervised
Command Center. CALL FOR SERVICE appears
in any Command Center with text display
capability that loses communication with the
panel. SERVC KEYPAD appears at all other
Command Centers connected to the system.
You can connect a total of 32 Command Centers
to the system. The number of supervised
Command Centers, number of areas, and the
available power affect the total number of
Command Centers you can connect to the
system. See Command Center in the D9000/
D7000 Series Program Entry Guide (74-07695-
000) for complete programming details on
Command Center options.
There are four Command Centers available for
use with the system. The D1255 features a 16-
character alphanumeric display for general use.
The D1256 is also a text display Command
Center with functional keys optimized for local fire
alarm control. The D1257 is a text display
Command Center for fire annunciation. The D720
is an LED display Command Center appropriate
for use as a single area Command Center with
up to eight points.
See the User's Guide (71-06150-000) for
operational information.
74-07692-000-C
www.PDF-Zoo.com

Arming Devices

29
to
D9000/D7000 Series Operation & Installation Manual
4/97
firealarmresources.com

Assigning the Command Center an Address

Switches on the Command Center assign an
address (1 to 8) to the Command Center. The
address determines if the Command Center is
supervised, the Command Center's scope, and
what area the Command Center is assigned to.
See Command Center Assignment in the D9412/
D9112 Program Entry Guide (74-07695-000) for
a complete description of addresses.
32
Table 5 shows the correct switch setting for each
address.
1
Address #1
ON
Address #2
OFF
2 TM
Address #3
ON
Address #4
OFF
Address #5
ON
Address #6
OFF
Address #7
ON
Address #8
OFF
Table 5: Command Center Address Settings

Installation

Consult the Command Center installation
manuals for installation and mounting
instructions. Command Centers connect to the
panel in parallel as shown in Table 6.
D9412/D9112
Terminal
Function
32 *
POWER +
31
DATA BUS A
30
DATA BUS B
29
COMMON
*Connect with at least 5' of 22 AWG wire (14' of 18 AWG wire)
Table 6: Command Center Connections
Page 37
Switch
2
3
4
5
6
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
Command Center
Wire Color
Function
Red
12 VDC
Yellow
Data-In
Green
Data-Out
Black
Common