Part 15 of FCC rules for Class B Computing Devices. Do not install the D2212 on public coin service provided by the telephone company. Connection to Party Line service is If this equipment causes interference to radio or television...
Introduction Table of Contents D2212 Control/Communicator Introduction ................ 3 The Radionics D2212 Control/Communicator is shipped pre- D2212 Control/Communicator ........3 assembled from the factory. You should receive the following Ordered Separately ............3 Enclosure Options ............4 parts with your D2212 panel.
Wire length for Points is limited only by the resistance on the Enclosure Options loop and potential EMI (Electro-Magnetic Interference) The D2212 is shipped in the D2203 enclosure. If you want to problems. mount the D2212 in one of the optional enclosures listed below, order the D2212M and the enclosure of your choice.
Radionics does not recommend a telephone or electrical ground for the earth ground connection. Use 18 AWG wire maximum under the terminal. Use a spade lug or splice for larger wire.
D2212 Keypad Diagnostics manual (74-07385-000). Point 1 Terminals 13 and 14 Point 1 on the D2212 is a powered, supervised point. External Relays Terminals 11 and 12 The panel monitors the Point 1 sensor loop for normal, You can program terminals 11 and 12 to provide outputs for shorted, or open conditions.
Programming for each point determines terminal 6 (alarm output). See Figure 5. Program the relay how the panel responds to these conditions. See the D2212 for Function 3 to provide annunciation of troubles for all fire Program Entry Guide .
Lead Acid Batteries Only: The panel charging circuit is Fill out the Point Chart only calibrated for lead-acid batteries. Do not use gel-cell or Radionics recommends that you fill out the Point Chart on nicad batteries. the Installation Label located on the inside of the D2203 Enclosure cover.
The panel can be programmed to use DTMF or pulse short circuits on both the auxiliary and alarm power outputs. dialing. See Phone Parameters in the D2212 Program Entry Guide . Bell circuit protection: A short on the alarm power output...
Shorted Loop = Greater than 0.0 VDC, but less than Easikey 2.0 VDC. You can use a Radionics Easikey access system to turn the system Off. Program the Keyswitch prompt to Easikey (see Points 7 and 8 the D2212 Program Entry Guide for instructions). You must Points 7 and 8 are not supervised with EOL resistors.
It is suitable for Central Station, Grade B applications you may contact the detector manufacturer. when the Model D2212 DACT unit is installed with a UL Listed local sounding device. Also suitable for Central Station Mercantile, Grade Test weekly: Radionics recommends testing fire and combined fire/ AA applications when installed with the Model D8122 derived burglary systems weekly.
D8130 Release Module Optional The D2212 is not listed for these applications: Local Fire/Burglary Combined, Local Fire, Local and Central Station Fire Combined, Local and Central Station Fire/Burglary (Grade C), Central Station Fire/Burglary (Grade C), Central Staion Fire, and Electrically Actuated Transmitter.