D9000/D7000 Series Control/Communicator Installation and Troubleshooting Quick Reference Introduction This reference contains the very basic information a trained installer needs to install and troubleshoot a D9000/D7000 Series Control/Communicator system. See the D9000/D7000 Series Operation and Installation Manual (74-07692-000) and the D9000/D7000 Series Approved Applications Compliance Guide (74-07693-000) for a complete description of the D9000/D7000 Series Control/Communicator and detailed installation instructions.
Basic Troubleshooting Service Walk Test Shows Extra Points The Service Walk Test differs from the standard Walk Test in that POPITs whose switches are set for a point number not programmed in the panel appear in the test. Service Walk Test only available at Command Centers with panel wide scope: See Command Center in the D9000/D7000 Series Control/Communicator Program Entry Guide (74-07695-000) for a description of Command Center scope.
Page 3
SE RV IC E WA LK ? E N T 246 P TS TO TES T Test a d evice P O IN T TE XT (Text d isplays 60 se co nds) 2 45 PT S TO TE ST Test a d evice PO IN T T E XT (Text d isplays 60 se co nds)
Problems with Points If you incorrectly set the switches on a POPIT you may create both a missing and extra point. When you find a missing point, perform a Service Walk Test to search for extra points. See the Owner’s Manual (71-06150-000) for test instructions. Symptom Diagnosis Remedy...
Page 5
Problems with Points (Continued) Symptom Diagnosis Remedy One or more The sensor loop is Remove the sensor loop from the points remain in open, shorted, or D9412/D9112 or POPIT and meter it for trouble or alarm grounded. continuity. There should be no more than with all devices 100 ohm resistance, plus the value of the Opens,shorts, or...
Page 6
Problems with Points (Continued) Symptom Diagnosis Remedy All off-board Short on Aux Power, Terminals 3 and 24 share a common circuit points are terminal 3 or ZONEX breaker. Check wiring and devices connected MISSING. power, terminal 24. to these terminals for shorts or grounds. If only one POPEX Check POPEX module for correct connections module is connected...
Problems Programming the Panel Before attempting to program the panel, you should be familiar with the basic operation of the D5200 programmer. See the D5200 Operation Manual (74-06176-000). If you still experience problems, check for the symptoms below. Symptom Diagnosis Remedy The programmer The programmer is...
Verify that the receiver is compatible answers the call compatible with the with the format the D9412 is using and provides an D9412/D9112 (either BFSK or Radionics Modem initial “handshake” transmission format. IIIa ™ Communications Format). See Phone in the D9412/D9112 Program acknowledgment, Entry Guide (74-07695-000).
Page 9
Communications Failure (Continued) Symptom Diagnosis Remedy The line rings but Line is not ringing at 1. Verify that the lines are correctly the D6500 the receiver. connected to the receiver. receiver does not 2. Verify that correct prefixes and phone pick up.