Radionics D2412 Installation Manual

Control / communicator

Advertisement

Quick Links

D2412 Control / Communicator
Installation Manual
8/11/97 P/N 35115B
© 1997 Radionics
www.PDF-Zoo.com
firealarmresources.com

Advertisement

Table of Contents
loading

Summary of Contents for Radionics D2412

  • Page 1 D2412 Control / Communicator Installation Manual 8/11/97 P/N 35115B © 1997 Radionics www.PDF-Zoo.com firealarmresources.com...
  • Page 2 1800 Abbott Street warranty. P.O. Box 80012 Salinas, CA 93912-0012 Do not install the D2412 on public coin service provided by the telephone company. Connection to Party Line service is subject to © 1997 Radionics, Inc. Salinas, CA, U.S.A. All rights reserved.
  • Page 3: Table Of Contents

    Table Of Contents Introduction ............ 4 Make the Telephone Connections ....10 D2412 Control / Communicator ......4 Power Up ............10 Ordered Separately .......... 4 Program the Panel ..........10 Enclosure Options ..........4 Unlock the Standby Switch ....... 10 Listings and Approvals ........
  • Page 4: Introduction

    000) • Three-wire data cable assembly (15-07032-000) Enclosure Options D205 Keypad The D2412 is shipped in the D2203 enclosure. If you want Each D205 includes the following: to mount the D2412 in one of the optional enclosures • D205 Keypad listed below, order the D2412M and the enclosure of your •...
  • Page 5: Listings And Approvals

    Mount it in the desired location. Be sure there is enough Listings and Approvals clearance to open the door for maintenance. Mount the panel into the enclosure a shown in Figure 1. The D2412 has the following approvals: Fire Underwriters Laboratories as a Household Fire and Run the Premises Wiring Burglary Warning System Control Unit for NFPA 72 (Chapter 2) Household Fire Warning.
  • Page 6: Connect To Earth Ground

    Radionics does not recommend a telephone or electrical ground for the earth ground connection. Use 18 AWG wire maximum under the terminal. Use a spade lug or splice for a larger wire.
  • Page 7: Continue Connections To The Panel

    Alarm Current available for the Alarm Output terminals. Primary Alarm Current - NSC current In formula format: required = Alarm Current available Figure 3: Keypad Wiring D2412 Installation Manual Page 7 8/11/97 P/N 35115B © 1997 Radionics www.PDF-Zoo.com firealarmresources.com...
  • Page 8: Auxiliary Power

    Devices powered from this output must operate over a range of 10.2 VDC to 13.9 VDC. Point 1 on the D2412 is a powered, supervised point. You must use a minimum of five feet (22 AWG) of wire The panel monitors the Point 1 sensor loop for normal, when connecting devices mounted outside the shorted, or open conditions.
  • Page 9: Points 2 To 6

    D133 (or D134) Relay Module. The relay module must be connected to one of the panel’s external relay outputs programmed for the reset function. See RELAYS in the Program Entry Guide for programming instructions. Figure 5: Points D2412 Installation Manual Page 9 8/11/97 P/N 35115B © 1997 Radionics www.PDF-Zoo.com...
  • Page 10: Point Expanders, Wired Or Rf

    RF Points RF Points transmit a radio frequency signal to Connect the battery and then plug in the transformer. an RF Receiver. The RF Receiver decodes the signal and sends the RF Point status to the D2412. Leave the Standby Switch locked down for now. Make the Telephone Connections...
  • Page 11: Fill Out The Delay Chart

    The panel transmits a BATTERY RESTORAL report. Primary (AC) Power Circuit A 16.5 VAC, 40VA transformer (Radionics model D1640) is the primary power source for the panel. The AC power circuit provides 1.5 Amps of rectified DC power.
  • Page 12: Power Outputs

    Investigate low battery reports right away : If primary D2412 and D8132 (or other power supply) must share (AC) power is off and the discharge continues, the panel COMMON : Note that Figure 10 shows the common from becomes inoperative when the battery voltage drops the D8132 module connected to both keypad’s common...
  • Page 13: Points

    Keyswitch Description You can connect a momentary contact arming station (keyswitch) to turn the D2412 on and off. Connect the keyswitch to any point sensor loop. You can use the external relay outputs and D133 (or D134) Relay Modules to activate arming status lights or keyswitch arming stations.
  • Page 14: Easikey Diagram

    Easikey You can use a Radionics Easikey access system to turn the system OFF. Program the Keyswitch prompt to Easikey. See the Program Entry Guide for instructions. You must use a 12 VDC option for the Easikey installation. See Easikey Installation and Operation Instructions .
  • Page 15: Installation Guide For Ul Applications

    Two-wire detectors must be electrically compatible, and The System Wiring Diagram, Issue A shows the relation- must be UL listed for use with the D2412. See the ship between the panel and the accessory components Radionics Technogram: Smoke Detectors Compatible referred to in the System Chart .
  • Page 16 Burglar Alarm, Grade C applications. Also suitable for Proprietary Burglar Alarm, Grade B applications when Model D2412 DACT unit is installed with a UL listed Local sounding device. Also suitable for Proprietary Burglar Alarm, Grade AA when the Model D2412 DACT unit is installed with a Model D8122 derived channel subscriber terminal unit.
  • Page 17: System Chart

    = At least one detector required. You can D262 Smoke Detector substitute other 2-wire detectors listed for 1• 1• Head use with the D2412. You could use the D261 Base D262 with the D270 four-wire base or D431, D435, D438, other manufacturer’s four-wire detectors. Opt.
  • Page 18: Current Rating Chart For Standby Battery Calculations

    * If Total A exceeds 1.0A (140mA for fire and combined fire/burglary systems, a stand-alone power supply is required to provide additional current. ** If Total C exceeds 860 mA, for fire systems, a stand-alone power supply is required to provide additional current. System Wiring Diagram, Issue A D2412 Installation Manual Page 18 8/11/97 P/N 35115B © 1997 Radionics www.PDF-Zoo.com...
  • Page 19: Specifications

    Auxiliary Power Output Compatible Accessories • 1.0A maximum at 10.2 VDC to 13.9 VDC for devices See the Radionics Product Catalog for complete list. powered at the Aux+ terminal (140mA for Fire and • D126 12V, 7 Ah Rechargeable Battery combined Fire/Burglary systems.
  • Page 20: D2412 Terminal Quick Reference

    Ring of incoming phone line. The Radionics logo is a registered trademark of Radionics, Inc., Salinas, CA, USA. © 1997 Radionics, Inc., Salinas, CA, USA. All rights reserved Radionics, Inc., 1800 Abbott Street, Salinas, California 93901 Customer Service: (800) 538-5807 www.PDF-Zoo.com...

Table of Contents