You can install the D811 in the enclosure with the
panel (see Figure 2) or in an adjacent enclosure
not more than 5 feet from the panel. Use 16 to 22
AWG wire.
Follow the procedure below to install D811
modules in the enclosure with the panel.
1. Align the D811 module with any of the four
mounting locations in the enclosure. See
Figure 2.
2. Use the screws provided with the module to
secure it in the enclosure.
Use the D137 Mounting Bracket to install D811
modules in enclosures with no module mounting
locations available.
C o ntro l/C o m m u n ic a to r
P an el
ZO N E X O U T 1
Z O N EX IN 1
Z O N E X O U T 2
Z O N E X IN 2
ZO N E X P O W E R +
ZO N E X C O M M O N
74-07692-000-C
4/97
www.PDF-Zoo.com
D 8 1 2 5
P O P E X
(-)
(-)
(+)
(+)
G N D
OU T
IN
A UX
28
27
26
25
24
23
(-)
(-)
(+)
(+)
G N D
O U T
IN
AU X
D 8 1 2 5
P O P E X

Figure 16: D811 Module Wiring

D9000/D7000 Series Operation & Installation Manual
Page 36
firealarmresources.com

Wiring Connections

Power down the panel to connect D811 modules
as shown in Figure 16. Note that the D811 for
relay number 53 connects to ZONEX 1. The D811
for relay number 117 connects to ZONEX 2 on
the D9412/D9112.
DATA
AUX
D 8 11 FO R R E L AY N U M B E R 5 3
GND
DATA
AUX
D 8 11 FO R R E L AY N U M B E R 11 7
GND
5
5
D9412/D9112 Only

Hide quick links: