Radionics D2012 Installation Manual

Control / communicator

Advertisement

Quick Links

D2012 Control / Communicator
Installation Manual
8/11/97 P/N 35122B
© 1997 Radionics
www.PDF-Zoo.com
firealarmresources.com

Advertisement

Table of Contents
loading

Summary of Contents for Radionics D2012

  • Page 1 D2012 Control / Communicator Installation Manual 8/11/97 P/N 35122B © 1997 Radionics www.PDF-Zoo.com firealarmresources.com...
  • Page 2 1800 Abbott Street warranty. P.O. Box 80012 Salinas, CA 93912-0012 Do not install the D2012 on public coin service provided by the telephone company. Connection to Party Line service is subject to © 1997 Radionics, Inc. Salinas, CA, U.S.A. All rights reserved.
  • Page 3: Table Of Contents

    Table Of Contents Introduction ............ 4 Make the Telephone Connections ....10 D2012 Control / Communicator ......4 Power Up ............10 Ordered Separately .......... 4 Program the Panel ..........10 Enclosure Options ..........4 Unlock the Standby Switch ....... 10 Listings and Approvals ........
  • Page 4: Introduction

    • Keypad Diagnostics Manual (35117) Enclosure Options D202A Keypad Each D202A includes the following: The D2012 is shipped in the D2803 enclosure. If you want • D202A Keypad to mount the D2012 in one of the optional enclosures • Installation Sheet (74-07118-000) listed below, order the D2012M and the enclosure of your •...
  • Page 5: Listings And Approvals

    Listings and Approvals top of the panel into the two retainer tabs. Once in the tabs, the panel will rest on the two support posts. Secure The D2012 has the following approvals: the panel with the supplied screws. Fire Underwriters Laboratories as a Household Fire and...
  • Page 6: Connect To Earth Ground

    The panel resets all its timers and counters, and clears all buffers. If the panel is armed, Radionics does not recommend a telephone or electrical releasing the standby switch causes the panel to disarm. ground for the earth ground connection. Use 18 AWG wire maximum under the terminal.
  • Page 7: Continue Connections To The Panel

    Output terminals. D126 Battery required for fire and combined fire/ burglary systems : In order to meet standby battery requirements, use the Radionics D126, 12 V 7.0Ah battery for fire and combined fire/burglary systems. Fire System Power Formula To calculate the current available at the Alarm Output...
  • Page 8: Auxiliary Power

    Connecting Two-wire Smoke Detectors to Point 1: Terminals 9 and 10 (Ext1 and Ext2) Connect up to 15 Radionics D262 two-wire smoke detectors to Point 1. Refer to the Technogram: Smoke You can program the External Relay terminals (terminals 9 Detectors Compatible with the D2812 (P/N 33123), for a and 10) to provide outputs for two external relays.
  • Page 9: Points 2 To 6

    D133 (or D134) Relay Module. The relay module must be connected to one of the panel’s external relay outputs programmed for the reset function. See RELAYS in the Program Entry Guide for programming instructions. Figure 5: Points D2012 Installation Manual Page 9 8/11/97 P/N 35122B © 1997 Radionics www.PDF-Zoo.com...
  • Page 10: Make The Telephone Connections

    Program the Panel transmits data. Use the Keypad, Radionics D5200 Programmer, or a After installation, confirm that the panel seizes the line, remote programmer to program the panel. See the acquires dial tone, reports correctly to the receiver, and Program Entry Guide for programming options and releases the phone line to the in-house phone system.
  • Page 11: Fill Out The Delay Chart

    Primary (AC) Power Circuit a trouble condition. The panel transmits a BATTERY LOW report. A 16.5 VAC, 25VA transformer (Radionics model D1625) is the primary power source for the panel. When the battery voltage returns to 13.0 VDC and there is AC power at the terminals labeled 16.5VAC, the keypad...
  • Page 12: Power Outputs

    Battery Charging Circuit D2012 and D8132 (or other power supply) must share Float Charge COMMON : Note that Figure 10 shows the common from The float voltage for the battery charging circuit is 13.9 the D8132 module connected to both keypad’s common VDC.
  • Page 13: Points

    It does not turn the system ON. Keyswitch Description You can connect a momentary contact arming station (keyswitch) to turn the D2012 on and off. Connect the keyswitch to any point sensor loop. Figure 12: Keyswitch You can use the external relay outputs and D133 (or...
  • Page 14: Easikey Diagram

    Easikey You can use a Radionics Easikey access system to turn the system OFF. Program the Keyswitch prompt to Easikey. See the Program Entry Guide for instructions. You must use a 12 VDC option for the Easikey installation. See Easikey Installation and Operation Instructions .
  • Page 15: Installation Guide For Ul Applications

    Two-wire detectors must be electrically compatible, and The System Wiring Diagram, Issue A shows the relation- must be UL listed for use with the D2012. See the ship between the panel and the accessory components Radionics Technogram: Smoke Detectors Compatible referred to in the System Chart .
  • Page 16 Burglar Alarm, Grade C applications. Also suitable for Proprietary Burglar Alarm, Grade B applications when Model D2012 DACT unit is installed with a UL listed Local sounding device. Also suitable for Proprietary Burglar Alarm, Grade AA when the Model D2012 DACT unit is installed with a Model D8122 derived channel subscriber terminal unit.
  • Page 17: System Chart

    = At least one detector required. You can D262 Smoke Detector substitute other 2-wire detectors listed for 1• 1• Head use with the D2012. You could use the D261 Base D262 with the D270 four-wire base or D431, D435, D438, other manufacturer’s four-wire detectors. Opt.
  • Page 18: Current Rating Chart For Standby Battery Calculations

    * If Total A exceeds 860 mA, a stand-alone power supply is required to provide additional current. ** If Total C exceeds 860 mA, for fire systems, a stand-alone power supply is required to provide additional current. System Wiring Diagram, Issue A D2012 Installation Manual Page 18 8/11/97 P/N 35122B ©...
  • Page 19: Specifications

    7.0 Ah battery required for Fire and combined Fire/ Burglary systems. Compatible Accessories See the Radionics Product Catalog for complete list. Auxiliary Power Output • 500mA maximum at 10.2 VDC to 13.9 VDC for devices • D126 12V, 7 Ah Rechargeable Battery powered at the Aux+ terminal (140mA for Fire and •...
  • Page 20: D2012 Terminal Quick Reference

    Ring of incoming phone line. The Radionics logo is a registered trademark of Radionics, Inc., Salinas, CA, USA. © 1997 Radionics, Inc., Salinas, CA, USA. All rights reserved Radionics, Inc., 1800 Abbott Street, Salinas, California 93901 Customer Service: (800) 538-5807 www.PDF-Zoo.com...