Testing the System

After finishing the installation and programming
of the panel, make a complete functional test of
the system. Test the panel and all devices for
proper operation. Test after you first program the
panel and after any subsequent programming
session.
Service Walk Test shows extra points: Use the
service walk test at a panel wide Command
Center to perform a complete test of the panel.
The service walk test function is similar to the
ordinary walk test function, with the additional
ability to display points that are not properly
programmed.
If you test a POPIT with it's switches set for a point
with a blank point index and/or no area
assignment, it appears as an extra point during a
Service Walk Test.
74-07692-000-C
4/97
www.PDF-Zoo.com
D9000/D7000 Series Operation & Installation Manual
Page 14
firealarmresources.com
If you test a device, and the panel doesn't
respond, there may be a problem with the device,
the wiring, the POPIT ID setting, or the
programming for the point. If you incorrectly set
the switches on a POPIT, you may create both a
missing and extra point. When you find a missing
point, performing a service walk test for extra
points may help diagnose the problem.
See the Trouble Shooting Section of this manual
for complete service walk test instructions.
Clear after test: To clear the event memory and
report buffer, momentarily close the reset pin.
Events stored in the panel's event log are not
cleared.