Firing rates

The MAXIMUM OUTPUT is chosen from within the continuous
diagram area (Fig. 2).
The MINIMUM OUTPUT must not be lower than the minimum
limit of the diagram:
GI/EMME 1400 = 407 kW
GI/EMME 2000 = 581 kW
GI/EMME 3000 = 872 kW
GI/EMME 4500 = 1163 kW
26
24
22
20
GI/EMME 2000
18
GI/EMME 1400
16
14
12
10
8
6
4
2
0
220 380 540
700 860 1020 1180 1340 1500 1660 1820 1980 2140 2300 2460 2620 2780 2940 3100 3260 3420 3580 3740
400 600
800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
4.8

Test boiler

The burner/boiler combination does not pose any problems if the
boiler is EC approved and its combustion chamber dimensions
are similar to those indicated in the diagram (Fig. 3).
If the burner must be combined with a boiler that has not been EC
approved and/or its combustion chamber dimensions are clearly
smaller than those indicated in the diagram, consult the
manufacturer.
The firing rates were obtained in special test boilers, according to
EN 676 standard.
20160907
Technical description of the burner
GI/EMME 4500
GI/EMME 3000
Thermal power
10
The firing rate value (Fig. 2) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
ATTENTION
shown on page 19.
3000
3200
3400
3600
In Fig. 3 you can see the diameter and length of the test
combustion chamber.
Example:
Output 7000 kW - diameter 120 cm - length 6 m
MODULATING RATIO
The modulating ratio, obtained in test boilers, according to
standard (EN 676 for gas, EN 267 for light oil), is of 4:1 for light
oil and 7:1 for gas.