5 - MAINTENANCE

5.8 - Preventive maintenance

All equipment must be serviced and commissioned by qualified personnel.
COMPONENT
FAN
MOTOR
DRIVE
FILTRATION
SOUND ATTENUATOR
COIL
HUMIDIFIER
This table relates to "standard" use of our units and is provided for guidance only. Servicing frequency rates must therefore be adjusted 
based on your conditions of use.

5.9 - Cleaning the units

On site: Keep the units wrapped for as long as possible. Upon unwrapping them, immediately make the air connections and keep the
boxes closed.
Before turning on and installation, vacuum the inside of the air handling units and, if necessary, clean the panels with a spray bottle
of solution and a soft cloth. Start up the system with just the prefilters (dust in the ducts, etc.). Wait a few hours; change the filters if 
necessary and then fit all the filter stages.
■ Cleaning in cleanrooms and associated controlled environments
Follow the procedures in force on the site of installation.
Cleaning and decontamination can be reduced to a strict minimum with the right filtration and by following the relevant procedures.
High-pressure washers are sources of contamination and therefore prohibited. Clean with either a spray bottle filled with a cleaning 
solution or disinfewwnt and soft cloth or special wipes.
Reminder: Contaminants may be brought in each time a door is opened in a cleanroom or associated controlled environment.
22
OPERATIONS REQUIRED
Check the cleanliness of the housing
Check the impellers or rotating parts (visual check)
Check the bearings (noise)
Lubricate (depending on fan)
Check the mounts (visual check)
Check the fasteners (visual check)
Check for corrosion
Check the bearings (noise)
Check the fasteners (visual check)
Check the connections
Check its condition. Replace if necessary.
Check the tension of the belts
Check the alignment
Check for vibrations and retighten the casing
Regularly check the fouling level
Check entire assembly for leaks
Replace
Check the cleanliness of the baffles
Check for tears in the baffles
Check the cleanliness
Check the level of antifreeze
Drain the coil
RECOMMENDATION
3 months
3 months
3 months
Every 20,000 to 30,000 hrs
3 months
3 months
6 months
3 months
3 months
6 months
3 months
3 months
3 months
3 months
3 months
3 months
as recommended by the manufacturer
3 months
3 months
3 months
varies by operating conditions
varies by operating conditions
see humidifier manual