Leading Sensor - flowair T-box Zone User Manual

Table of Contents

Advertisement

Leading sensor

Temperature sensor
ZONE 1
+
-
+
-
Active temperature sensor
Leading sensor is the sensor built in T-box
controller
Leading sensor is the local sensor. When it is
selected, operation of each unit is regulated
locally
The correction of sensor measurements is also possible.
ATTENTION: The settings apply only to a given
zone. Each zone should be set separately
14
Weekly programer
• For each day you can set up to 18 on/off events,
• Start time of new event is also the end time of previous event,
• For each event you can set any temperature for units, in the
range of 5 – 45
C,
o
• For each event you can set for KM and Cube an airflow and
dampers opening degree, for OXeN an airflow,
• Events for each day can be set individually or they can be
copied from day, which was already set.
Activation of weekly programer is signalized on main
screen via following icons:
Weekly programer active – SYSTEM ON
Weekly programer active – SYSTEM OFF
Weekly programer active – settings forced.
There were ad hoc set other parameters than
the settings programmed in the weekly
programer:
• desired temperature,
• airflow for OXeN,
• the airflow or degree of opening of the KM
and Cube dampers
• system were OFF and was turned on (to
turn on the system press and hold for 2 s the
calendar icon on main screen),
• system were ON and was turned off (to turn
off the system press and hold for 2 s the
calendar icon on main screen).
The ad hoc settings only apply to a given zone
and will be reset on transition
weekly programer for the next zone.
ATTENTION: The settings apply only to a given
zone. Each zone should be set separately