user manual

Advertisement

Table of Contents
loading

Summary of Contents for flowair T-box Zone

  • Page 1 T-box Zone user manual...
  • Page 2: Table Of Contents

    If temperature Time .......................8 sensor was chosen in a T-Box menu as „installed in unit”, Date ........................8 T-box Zone controller can be mounted out of area i.e. Integrated units ..................8 technical room. Zones ......................9 Delete zones .....................9...
  • Page 3: Installation

    800 m* DRV - SW2 ADDRESS SETTING * Applies to all devices connected to T-box Zone controller in line ** In case of Cube devices addressing is beeing done by service during first startup Last DRV Others DRV...
  • Page 4: First Run

    FIRST RUN Selection of language Date 2021 August Setting of date Selection of language Time Zones Setting of time Setting the number of zones A maximum of 31 zones can be set www.flowair.com...
  • Page 5 • if the SW2 dipswitch on the last device in line is set to T120 position (in Cube devices, the dipswitch is set by the service during the first start-up). www.flowair.com...
  • Page 6 … Remote temperature setting Navigation between Navigation between groups of devices zones By default, all devices are assigned to Zone 1. Go to the next zone to assign devices to it. Press to assign the device to the zone www.flowair.com...
  • Page 7: Main Screen

    Short press zones menu Searching for units Controller lock Setting of desired temperature Number of zones BMS settings 1 2 3 Weekly programer active Language selection Settings lock active BMS mode active Measured temperature Set temperature Alarms Zone names Z1 www.flowair.com...
  • Page 8: Time

    Time Time Device assigned to a given zone Device assigned to another zone Press the button to assign to a given zone Long press displays information about the DRV software version of the device Setting of time www.flowair.com...
  • Page 9: Zones

    Zone with devices assigned Z 02 Delete zones Zone without devices assigned Z 01 Zone with devices assigned Zone marked for deletion Z 03 Z 02 Zone without devices assigned NOTE: Only zones without assigned devices can be deleted. www.flowair.com...
  • Page 10: Language

    Language System information Selection of language System information T-box Zone v 20.45 Compilation v 20.45-gc2044a-9+ 07/11/2020, 13:13 … Basic information about software and hardware version Active language Reset Confirm choice BAUD 9600 FRAME 8E1 ID – setting unit adress: from 1 to 247 Restore default settings BAUD –...
  • Page 11: Controller Lock

    Free 4-digit password can be set. Antifreeze function in a given zone After returning to main screen and 30 s of inactivity, Leading sensor in a given zone controller will be locked automatically Settings for external potential-free input EXT. www.flowair.com...
  • Page 12 Change name Zone devices A B C Zone devices Change name ZONE 1 ZONE 1 … Zone rename Device activated - working Device activated - not working Device activated - failure Device deactivated - not working www.flowair.com...
  • Page 13: Antifreeze

    ATTENTION: The settings apply only to a given zone. Each zone should be set separately. ATTENTION: The settings apply only to a given zone. Each zone should be set separately www.flowair.com...
  • Page 14: Leading Sensor

    The ad hoc settings only apply to a given zone and will be reset on transition weekly programer for the next zone. ATTENTION: The settings apply only to a given zone. Each zone should be set separately www.flowair.com...
  • Page 15 OXeN - additional OXeN group settings Robur KM - additional ROBUR with mixing chamber Removing the events group settings Cube - additional Cube group settings Copying events on the another zones Event – system On Event – system Off Moving to the next day www.flowair.com...
  • Page 16 When the dampers are closed (no ventilation), it is possible to select the operating mode of the fan after reaching desired temperature. Fan can operate continuously or be turned off. www.flowair.com...
  • Page 17 When Auto mode is activated, the Cube’s dampers will be adjusted automatically until Weekly programer - Delete task the set temperature is economically reached. Auto Weekly programer Delete task 7:00 16:00 16:15 22:30 Events marked for deletion 16:15 22:30 www.flowair.com...
  • Page 18 Selected zones to which the work schedule from zone Z1 will be copied A zone in which a work schedule is already programmed, you can also copy the settings from zone Z1 to it A zone in which no work schedule has been programmed yet www.flowair.com...
  • Page 19: Leo Fan Heaters

    Readings measured temperature is higher than desired temperature Ventilation – valve is constantly closed, fan operates continuously at selected speed Auto – automatic fan regulation depending on desired and measured temperature Manual – fan operates with constant, selected speed www.flowair.com...
  • Page 20 1, 2, 3 or be turned off - select OFF. Airflow AUTO In AUTO mode after reaching desired temperature fan can operate continously on selected step: 1, 2, 3 or be turned off - select OFF. www.flowair.com...
  • Page 21 The heater must be equipped with T3 sensor (optional equipment). Activation of destratification mode Setting of temperature difference (difference between temperature under the ceiling and temperature in the occupied zone), at which LEO heaters will be turned on Selection of heaters, which should operate in destratification mode www.flowair.com...
  • Page 22 Readings Readings ON/OFF Temperature Temperature in valve the room under the ceiling To read temperatures near the unit, external tempera- ture sensors PT-1000 must be connected to DRV control module. www.flowair.com...
  • Page 23: Leo Cool Fan Cooler/Heater

    Cooling – cooling medium valve is opened when measured temperature is higher than desired temperature Ventilation – valve is constantly closed, fan operates continuously at selected speed Auto – automatic fan regulation depending on desired and measured temperature Manual – fan operates with constant, selected speed www.flowair.com...
  • Page 24 LEO COOL selected step: 1, 2, 3 or be turned off - select OFF. Airflow AUTO In AUTO mode after reaching desired temperature fan can operate continously on selected step: 1, 2, 3 or be turned off - select OFF. www.flowair.com...
  • Page 25 Readings LEO COOL Readings ON/OFF Temperature in valve the room To read temperatures near the unit, external tempera- ture sensors PT-1000 must be connected to DRV control module. www.flowair.com...
  • Page 26: Leo El Electric Heaters

    Heating power setting Automatic fan and heaters power Heating regulation depending on desired Selection of operating mode and measured temperature Manual regulation of airflow and heaters power Destratification Ventilation – heaters are off, fan operates Readings at selected speed continuously www.flowair.com...
  • Page 27 Airflow setting during operation in manual mode Heating power setting - 3 steps In MANUAL mode after reaching desired Heating power setting - 2 steps temperature fan can operate continously on selected step: 1, 2, 3 or be turned off - select OFF. www.flowair.com...
  • Page 28 The heater must be equipped with T3 sensor (optiona- lequipment). Activation of destratification mode Setting of temperature difference (difference between temperature under the ceiling and temperature in the occupied zone), at which LEO heaters will be turned on Selection of heaters, which should operate in destratification mode www.flowair.com...
  • Page 29 Readings LEO EL Readings Temperature under the ceiling Temperature in the room To read temperatures near the unit, external temperature sensors PT-1000 must be connected to DRV control module. www.flowair.com...
  • Page 30: Km Mixing Chambers

    Cooling – valve is opened when measured temperature is higher than desired temperature Readings Filters operating status Ventilation – valve is constantly closed, fan operates continuously at selected step Selection of leading sensor Roof fan setting Dampers setting according to external temperature www.flowair.com...
  • Page 31 • 2 - second level of control active in given weekly programer zone. When the dampers are closed (no ventilation), it is possible to select the operating mode of the fan after reaching desired temperature. Fan can operate continuously or be turned off. www.flowair.com...
  • Page 32 • 1 - first level of control When the dampers are closed (no ventilation), it is • 2 - second level of control possible to select the operating mode of the fan after reaching desired temperature. Fan can operate continuously or be turned off. www.flowair.com...
  • Page 33 Temperature in the room ON – automatic setting of dampers according to external temperature is active – see p. 37 Temperature of air supplied into the room Dampers opening degree ON/OFF valve Temperature of heating medium on return pipe www.flowair.com...
  • Page 34 SRX3d valve opening degree. Correction of air temperature set on main screen The value should be set depending on the degree of dirtiness/ contamination of the facility. www.flowair.com...
  • Page 35 Positive value means that the roof fan removes more air than the KM supplies (under-pressure). Setting „+100%” means continuous operation of the roof fan. Negative value means that the roof fan removes less air than the KM supplies (overpressure). Setting „-100%” means operation of the KM only. www.flowair.com...
  • Page 36: Leo D Destratificators

    Settings of auto operating mode air down to occupied zone. When amount of heat is insufficient, LEO heaters are turned on automatically. Manual – destratificator operates in ON/OFF mode. It is turned on when temperature under the ceiling is higher than set temperature. www.flowair.com...
  • Page 37 To read temperatures near the unit, external tempera- ture sensors PT-1000 must be connected to DRV control Settings of manual operating mode module. MANUAL settings Destratificator operates in ON/OFF mode. It is turned on when temperature under the ceiling is higher than set temperature. www.flowair.com...
  • Page 38: Robur Gas Heaters

    Heating-continuous - after reaching the set Thermal protection settings temperature, the fan works continuously Heating-manual – manual selection of the burner power Ventilation mode - fan is working continuously, burner is off Unit is off www.flowair.com...
  • Page 39 Heating power Thermal protection ROBUR ROBUR Heating power Temp. alarm Burner power setting in heating-manual mode Max. operating temperature Temperature ready for restart Readings ROBUR Readings Outlet air temp. Temperature in the room www.flowair.com...
  • Page 40: Robur Km Mixing Chambers

    Heating-continuous - after reaching the set temperature, the fan works continuously Readings Heating-manual – manual selection of the burner Thermal protection settings power Ventilation mode – fan is working Filters operating status continuously, burner is off Unit is off Roof fan setting www.flowair.com...
  • Page 41 It is possible to change it ad hoc only. Change will only be active in given weekly programer zone. Dampers setting in heating and ventilation mode Dampers setting in heating-continues mode www.flowair.com...
  • Page 42 • normal operation status External temperature • 1 - first level of control • 2 - second level of control Temperature in the room Dampers opening degree On – automatic setting of dampers according to external temperature is active. www.flowair.com...
  • Page 43 Value must be reset. Alarm does not affect the operation of the unit. Temperature ready for restart Filters operating time limit ROBUR KM Filters The value should be set depending on the degree of dirti- ness/ contamination of the facility. www.flowair.com...
  • Page 44 ROBUR KM supplies (under-pressure). Setting „+100%” means continuous operation of the roof fan. Negative value means that the roof fan removes less air than the ROBUR KM supplies (overpressure). Setting „-100%” means operation of the ROBUR KM only. www.flowair.com...
  • Page 45: Elis Air Curtains

    Door sensor has a priority. Without it’s signal unit will not run Antifreeze Heating – valve is opened when measured temperature is lower than desired temperature Ventilation – valve is constantly closed, fan operates continuously at selected step www.flowair.com...
  • Page 46 K2 work program) the curtain fan can operate at sible to set ∞ value, then valve is constantly open. the selected speed for a specified time or be turned Valve delay time must be shorter than fan delay off - select OFF. time. www.flowair.com...
  • Page 47: Elis Duo Air Curtain-Fan Heater Combo Units

    Airflow setting for fan heater part – 3-steps Readings Selection of operating mode Setting of delay times ELiS Readings Readings Antifreeze To read temperatures near the unit, external tempera- ture sensors PT-1000 must be connected to DRV control module. www.flowair.com...
  • Page 48 Heating – valve is opened when measured temperature is lower than desired temperature Ventilation – valve is constantly closed, fan operates continuously at selected step Fan heater operates always according to temperature set on the controller, regardless K1/K2 mode. www.flowair.com...
  • Page 49 1, range 0:00 - 10:00 minutes, every 0:30 s. Value ∞ - valve is constantly open. 2, 3 or be turned off - select OFF. Valve delay time must be shorter than fan delay time www.flowair.com...
  • Page 50 Temperature in the room ON/OFF valve fans stops and valve is open to 100%. The unit must be equipped with T3 sensor (optional equipment). To read temperatures near the unit, external tempera- ture sensors PT-1000 must be connected to DRV control module. www.flowair.com...
  • Page 51: Slim Air Curtains

    Door sensor has a priority. Without it’s signal unit will not run Antifreeze Heating – valve is opened when measured temperature is lower than desired temperature Ventilation – valve is constantly closed, fan operates continuously at selected step www.flowair.com...
  • Page 52 K2 work program) the curtain fan can operate at sible to set ∞ value, then valve is constantly open. the selected speed for a specified time or be turned Valve delay time must be shorter than fan delay off - select OFF. time. www.flowair.com...
  • Page 53 PT-1000 must be connected to DRV control fans stops and valve is open to 100%. The unit must be module. equipped with T3 sensor (optional equipment). Temperature in ON/OFF valve the room www.flowair.com...
  • Page 54: Oxen Heat Recovery Units

    Operation without heat recovery – supply air is directed via by-pass without heat recovery („freecooling”/„free-heating”). Selection of leading sensor Automatic change of operating mode with or This icon informs that dampers are during without heat recovery, depending on temperature change of position, fans are stopped www.flowair.com...
  • Page 55 Change will only be active Three values of airflow should be definied: in given weekly programer event. • normal operation status • 1 - first level of control • 2 - second level of control www.flowair.com...
  • Page 56 Desired temperature of supply air External temperature Temperature in the room Temperature of removed air Temperature of air supplied into the room ON – status of by-pass dampers Temperature of heating medium ON – status of external dampers on return pipe ON/OFF valve www.flowair.com...
  • Page 57 SRX3d valve opening degree. Correction of air temperature set on main screen The value should be set depending on the degree of dirtiness/ contamination of the facility. www.flowair.com...
  • Page 58: Oxen El Heat Recovery Units

    Filters operating status recovery(„freecooling”/„free-heating”) This icon informs that dampers are during Automatic setting of heating power change of position, fans are stopped this AUTO icon informs also that fans are cooling the heater Manual setting of heating power MANUAL www.flowair.com...
  • Page 59 OXeN EL OXeN EL Readings Readings External temperature ON – status of by-pass damper Temperature in the room ON – status of external dampers Chosed of heating power Temperature of air supplied into the room Temperature of removed air www.flowair.com...
  • Page 60 OXeN EL Airflow 100% Appearance of this icon informs that the airflow setting has been defined in the weekly programer. It is possi- ble to change it ad hoc only. Change will only be active in given weekly programer event. www.flowair.com...
  • Page 61 After reaching the limit of working hours, there will be- The value should be set depending on the degree of dirtiness/conta- displayed an indication in alarm menu. Value must be reset. mination of the facility. Alarm does not affect the operation of the unit. www.flowair.com...
  • Page 62: Cube Rooftop Units

    Auto setpoint for cooling or heating depending on the active operating mode of the Cube. For cooling, optimal airflow is horizontal and for heating it is vertical manual mode - fixed swirl diffuser setting Manual Manual www.flowair.com...
  • Page 63 The selection of the leading/master sensor from: supply air, exhaust air and wall temperature sensors is made during first startup. It is also possible to define built in sensor in T-box sensor he leading sensor www.flowair.com...
  • Page 64 The change will only be active • 2 - second level of control in a given weekly programer zone manual setting of the recirculation damper position Manual position of the recirculation damper is changed automatically depending on air Auto temperatures www.flowair.com...
  • Page 65 Temperature of the air exhausted from the Current swirl diffuser setting room Temperature at the return of the medium Airflow Room temperature reading from the T-box controller’s built-in sensor or from the optional NTC wall-mounted sensor, connected to the Cube control box/enclosure www.flowair.com...
  • Page 66 Forcing - active signal from an external detector (option) Thermostat - the device works in thermostatic mode NightCool - the device works in the night cooling mode (applies to Climatix regulation) Overrun - cooling down process Defrosting - defrosting the heat pump (optional) www.flowair.com...
  • Page 67: Alarms

    T4 Addressing failure. Check DRV group Temperature check the temperature sensor binary address set in DRV and error sensor T5 use search button again check the fuse of the roof fan Roof fan fuse on theDRV board www.flowair.com...
  • Page 68 Forcing damper depending on the outside ture sensor sensor temperature no communication between DRV of fan heater part of DUO heater not ELiS DUO, check connection connected between DRV of air curtain part and DRV of fan heater part www.flowair.com...
  • Page 69 +48 58 669 82 20, fax: +48 58 627 57 21 e-mail: info@flowair.pl www.flowair.com Declaration Of Conformity UE FLOWAIR hereby declare that the T-box controller were produced in accordance to the following Europeans Directives: 2014/30/UE – Electromagnetic Compatibility (EMC) 2014/35/UE –...
  • Page 70 www.flowair.com...