7½- to 12½-ton self-contained packaged heat pump

Advertisement

P
S
roduCt
PeCifiCationS
r
C
i
— r
oof
urB
nStallation
Provisions for forks have been included in the unit base frame. No other
fork locations are approved.
• Unit must be lifted by the four lifting holes located at the base frame
corners.
• Lifting cables should be attached to the unit with shackles.
• The distance between the crane hook and the top of the unit must not
be less than 60".
• Two spreader bars must span over the unit to prevent damage to the
cabinet by the lift cables. Spreader bars must be of sufficient length
so that cables do not come in contact with the unit during transport.
Remove wood struts mounted beneath unit base frame before setting
unit on roof curb. These struts are intended to protect unit base frame
from fork lift damage. To remove the struts, extract the sheet metal
retainers and pull the struts through the base of the unit. Refer to rig-
ging label on the unit.
Important: If using bottom discharge with roof curb, duct-work should
be attached to the curb prior to installing the unit. Duct-work dimensions
are shown in Roof Curb Installation Instructions Manual.
Refer to the Roof Curb Installation Instructions
for proper curb installation. Curbing must
be installed in compliance with the National
Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb.
While rigging the unit, the center of gravity will
cause the condenser end to be lower than the
supply air end.
Bring condenser end of unit into alignment with
the curb. With condenser end of the unit resting
on curb member and using curb as a fulcrum,
lower opposite end of the unit until entire unit is
seated on the curb. When a rectangular cantilever
curb is used, take care to center the unit. Check
for proper alignment and orientation of supply
and return openings with duct.
7½-Ton
Unit Weights
Weights (lbs)
Weight A
Weight B
Weight C
Weight D
Shipping Weight
1175
Operating Weight
1135
Note: These weights are calculated without accessories installed.
26
igging
30"
8½-Ton
Weights (lbs)
285
345
285
325
285
320
285
300
1310
1285
www.goodmanmfg.com
Compressor 1
Compressor 2
49"
Corner & Center-of-Gravity Locations
10-Ton
12½-Ton
Weights (lbs)
Weights (lbs)
345
435
325
345
320
300
300
240
1310
1350
1285
1325
Return
Evaporator Coil
Supply
SS-CPH90-150