Transfer Switch Will Not Automatically Recharge Switches - Eaton Cutler-Hammer O & M Manual

Fixed spb automatic transfer switch
Hide thumbs Also See for Cutler-Hammer:
Table of Contents

Advertisement

Page 20
Step 5: Measure voltage between terminals A1 and A2
on the emergency switching device (spring
release coil). Does the voltage measure 120
VAC ± 10 volts? Record reading.
If YES:
Check spring release coil in emergency
switch.
If NO:
Check wiring to A1 and A2.
6.2.4 TRANSFER SWITCH WILL NOT AUTOMATI-
CALLY RECHARGE SWITCHES
Step 1: Measure the voltage between the terminals A6
and A2 on the switching device that does not
automatically recharge. Does the voltage read
120 VAC ± 10 volts? Record reading.
If YES:
Check electrical operator inside the
switching device.
If NO:
Verify wiring to A6 and A2.
Step 2: If problem persists contact Cutler-Hammer.
IB01602002E
Effective 10/02