Installation; Lens Options - LEGRAND Wattstopper FSP-301 Installation Instructions Manual

Low voltage pir continuous dimming fixture integrated sensor with bluetooth low energy technology
Table of Contents

Advertisement

Available languages

Available languages

INSTALLATION

1. Determine an appropriate mounting location inside the light
fixture minimizing the electric light contribution to the sensor's
photocell. Allow a minimum distance of 0.2" (5.1mm) from the
wiring end of the sensor to the wall of the fixture.
2. Drill a hole 1.30" (33.0mm) in diameter through the sheet metal
in the bottom of the fixture.
3. Add the rubber gasket to the threaded collar, and install the
sensor face down, parallel to the mounting surface. Ensure the
rubber gasket touches the inside surface of the fixture. Install
the nut (or optional collar) securely against the fixture to a
torque of 25–30 in-lbs to ensure the lens is installed properly.
4. Align the locking features between the sensor and lens module
and push the lens module forward until the o-ring seals firmly.
Turn the lens module clockwise to ensure that it locks in place.
5. Connect wires as shown in the wiring diagram.
6. Restore power from the circuit breaker.
NOTE: An optional collar can be installed in place of the tightening
nut. See the Ordering Information table on page 4 for
details.
Several lenses are available for use with the FSP-301. Lenses give coverage at mounting heights between 8' – 40' for applications such
as offices, warehouses, and outdoor use. Density and range of the coverage is determined by the type of lens and mounting height.
A lens with shroud option is also available. The shroud blocks light coming from the fixture, to prevent interference with the photocell
function of the sensor. Lens modules are IP-66 rated when combined with an FSP-301 sensor mounted to an IP-66 rated outdoor
fixture. See the FSP-Lx Coverage Guide for more information.
OUTDOORS—USE AT THE EXPOSED SENSOR COLLAR PART ONLY WHEN INSTALLED AT THE SPECIFIC LOCATION PER
Ground
Non-Dimming
Driver
CTRL (Blue)

LENS OPTIONS

INSTALLATION INSTRUCTIONS WITH A LISTED OUTDOOR ENCLOSURE.
Neutral
Line
BZ-200 Power Pack
120 – 277 VAC (1 φ ), 50/60 Hz
20A Ballast/ELV/MLV/Tungsten/LED
LISTED
16A E-Ballast/CFL
Appliance
1HP @ 120/240VAC
Control
88T9
20A 120VAC Plug Load – Receptacle
Class 2 Output
Power Pack
Red
Lighting
Neut.
White
Load
24 VDC, 225 mA
Switch
Black
Red
Hot
Green
UL 2043 Plenum Rated
Ground
Control
Common
Any 3-Wire
24VDC
+24VDC
Sensor
www.legrand.us 800.879.8585
Class 2
16094r1
wiring only
+VDC (Red)
COM (Black)
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
Inside Fixture
Wall
Tightening Nut
(or Optional Collar)
NOTE: The Outside Fixture Wall thickness should be no
greater than 0.125" (3.18mm) for optimal sensor
mounting and security.
WIRING
Dimming
Driver
0-10V – (Pink)
0-10V + (Purple)
NOTE: Per UL, the 0-10V negative
dimming wire color has been changed
from gray to pink.
2
Rubber
Gasket
Outside
Tightening Nut
Fixture Wall
(or Optional Collar)
Lens Assembly
Ground
BZ-200 Power Pack
120 – 277 VAC (1 I ), 50/60 Hz
20A Ballast/ELV/MLV/Tungsten/LED
16A E-Ballast/CFL
1HP @ 120/240VAC
20A 120VAC Plug Load – Receptacle
Class 2 Output
24 VDC, 225 mA
UL 2043 Plenum Rated
Class 2
wiring only
CTRL (Blue)
+VDC (Red)
COM (Black)
Rubber
Fixture
Gasket
Wall
Neutral
Line
LISTED
Appliance
Control
88T9
Power Pack
Red
Lighting
Neut.
White
Load
Switch
Black
Red
Hot
Green
Ground
Control
Common
Any 3-Wire
24VDC
+24VDC
Sensor
www.legrand.com • 800.879.8585
16094r1