Danfoss Turbocor TTS Series Applications And Installation Manual page 27

Twin-turbine
Hide thumbs Also See for Turbocor TTS Series:
Table of Contents

Advertisement

From the outlet of the orifices, the refrigerant is directed to the heatsink plate of the inverter and to the underside of
the SCR heatsink. The refrigerant also passes through grooves surrounding the motor stator. As the refrigerant flows
through the grooves, it vaporizes into a gas. At the coil outlet, the refrigerant gas is channeled back to the suction
inlet via the motor cavity, thereby cooling the rotor. All models with the exception of the TTS300 and TGS230 use a
split-cooling method where the motor and electronics portions are cooled separately by refrigerant liquid.
Figure 3-3 Compressor Cooling Circuit (TGS230 / TTS300)
Table 3-3 Compressor Cooling Circuit (TGS230 / TTS300)
No.
Description
1
From Motor Winding Temp Sensor
2
BMCC
3
Solenoid M
4
Solenoid E
5
Liquid Refrigerant Inlet
6
Orifice
7
From Inverter Temp Sensor
No.
Description
8
SCR
9
Motor/Rotor Cooling Gas and Leakage
10
Cooling path re-enters at the suction line of the chiller
11
Pressure Regulating Valve
12
Cooling path redirects outside of the compressor
13
From Motor Cavity Temp Sensor
14
Inverter
M-AP-001-EN Rev. S-9/8/2021 Page 27 of 136