Figure 6 Outline Drawing, 625-800Kva Liebert Exl Single-Module Ups - Emerson Liebert eXL Installation Manual

625-800kva, 1.0pf, 60hz, three-phase, single-module
Table of Contents

Advertisement

Figure 6
Outline Drawing, 625-800kVA Liebert e XL single-module UPS
Rectifier\DC
Cable Entry, Area
With Panel Removed
12.5" x 21.9"
(318mm x 556mm)
Low Voltage Cable
Entry \ Exit, Area
With Panel Removed
8.8" x 9.8"
(224mm x 250mm)
1.4" (37mm)
To Frame Typ
Opposite Side
1.6" (40mm)
Low-Voltage Cable
Entry\Exit, Area
With Panel Removed
4.9" x 21.8" (125mm x 553mm)
33.9"
(862mm)
Input
Notes
1. 24" (610mm) minimum clearance above unit required for air exhaust,
and 36" (914mm) front access required for service.
2. Keep cabinet within 15 degrees of vertical while handling.
3. Top and bottom cable entry available through removable
access plates. Remove punch to suit conduit size and replace.
4. Unit bottom is structurally adequate for forklift handling.
5. Control wiring and power wiring must be run in separate conduits.
6. All wiring is to be in accordance with national and local electrical codes.
7. Width dimension includes side panels. Subtract 1.4" (35mm)
when removing both side panels.
8. See technical information drawing for shipping split weights.
®
Liebert
eXL
Panel to Frame
Typical
To Frame
Opposite
1.3" (33mm)
Side
14.3" (363mm)
to Frame
To Frame
2.4" (60mm)
Section A - (Top Looking Down)
123.6" (3140mm)
38.5"
51.2"
(978mm)
(1300mm)
Core
Core
Output/Bypass
FRONT VIEW
Bypass\Output
Cable Exit, Area
With Panel Removed
12.5" x 23.2"
(318mm x 590mm)
TOP VIEW
Rectifier\DC
Cable Entry, Area
With Panel Removed
(23.5" x 21.8"
(597mm) x 553mm)
BOTTOM VIEW
Bypass\ Output
Cable Exit, Area
With Panel Removed
10.9" x 28.4" (278mm x 722mm)
See
Bottom
View
U46-8C-2001
Rev. 3
18
Installation Drawings
To
Frame
1.3"
(33mm)
4" (101mm)
to Frame
To Frame
2.6" (65mm)
77.5"
(1969mm)
33.5"
(851mm)
34.4"
With Accent Strip
(874mm)
RIGHT SIDE VIEW

Advertisement

Table of Contents
loading

Table of Contents