Figure 11 Low-Voltage Cable Routing - Emerson Liebert eXL Installation Manual

625-800kva, 1.0pf, 60hz, three-phase, single-module
Table of Contents

Advertisement

Figure 11 Low-voltage cable routing

Low Voltage
Control Cable
Top Entry
Low Voltage
Wire Way
Bottom Entry
Low-Voltage
DOORS AND INNER SKINS REMOVED
Control Cable
Use these entry holes for
Liebert IntelliSlot
card cables only
Use these entry holes for
®
Liebert IntelliSlot
Unity
card cables only
Service Drawer
Provide at least 18" (457mm) of service loop
to all control connections to permit opening
the service drawer without removing the connections.
The extra service loop can either be left hanging
or loosely attached to the corner post.
Openings to Control Wire Way
To Ensure Isolation:
All wiring must have insulation rated
for 600V or higher.
• All cables not rated Class 1 must be
kept separated and secured away
from high-voltage Class 1 cables.
INPUT
®
Unity
21