CPS-2C USER'S GUIDE
on

Open Time 2 (POS 3)

off
TIMER
Open Time 2
This parameter is used to establish the duration of the run time for inlet 2
when it receives an opening demand. When Probe 2 Readout is above
Main Set Point 2, inlet 2 will wait for Open Delay 2 before opening for
Open Time 2. This parameter is adjusted in 1-second increments from 1 to
120 seconds.
Open Delay 2 Off D
This parameter is used to establish the duration of the idle time for inlet 2
when it receives an opening demand. When Probe 2 Readout is above
Main Set Point 2, inlet 2 will wait for Open Delay 2 before opening for
Open Time 2. This parameter is adjusted in 1-second increments from 5 to
600 seconds.
on

Close Time 2 (POS 4)

off
TIMER
Close Time 2
This parameter is used to establish the duration of the run time for inlet 2
when it receives a closing demand. When Probe 2 Readout is below Main
Set Point 2 – Differential 2, inlet 2 will wait for Close Delay 2 before
closing for Close Time 2. This parameter is adjusted in 1-second
increments from 1 to 120 seconds.
Close Delay 2 Off D
This parameter is used to establish the duration of the idle time for inlet 2
when it receives a closing demand. When Probe 2 Readout is below Main
Set Point 2 – Differential 2, inlet 2 will wait for Close Delay 2 before
closing for Close Time 2. This parameter is adjusted in 1-second
increments from 5 to 600 seconds.
HI
REC

Probe 2 Max (POS 5)

Probe 2 Maximum
This parameter displays the highest value reached by Probe 2 since the
CPS-2C was powered up or since this parameter was last cleared. To reset
this value to the actual Probe 2 Readout, press the SET/CLR button. The
Probe 2 Maximum is displayed to the nearest 0.1° from -58.0°F to 140.0°F
(-50.0°C to 60.0°C) or from -0.500''H
0.001''H
O.
2
Section C-26
O to 0.500''H
O to the nearest
2
2
CPS-2C