FS24X/FS20X DTM Manual, Issue 1
"xfer fnctn" (not writeable) Defines the transformation function that will be applied from
•
the Field Device Variable to the Analog Output, and Percent Range. The Transfer Function
does not affect the Digital Value representation.
"PV Damp" (not writeable)
•
Third "Tab": Detailed Setup
5.3.3
"PV" (not writeable)
•
"PV snsr unit" (not writeable)
•
"Max dev vars" (not writeable)
•
"PV class" (not writeable)
•
"PV LSL" (not writeable)
•
"PV USL" (not writeable)
•
"PV Min span" (not writeable)
•
"PV Damp" (not writeable)
•
"PV URV" (not writeable)
•
"PV LRV" (not writeable)
•
"PV xfer fnctn" (not writeable)
•
"PV % rnge" (not writeable)
•
"Loop current" (not writeable)
•
"AO Alrm typ" (not writeable)
•
"Channel flags" (not writeable)
•
"Loop current mode" can be used to enable/disable the relation between current and
•
measuring result. Default value is "Disabled". It can be changed to "Enabled".
"Poll addr" writes the HART polling address. Note: To avoid problems with double address
•
usage, please use the HART communication DTM to set HART polling addresses. See
§4.1.2
"Num req preams" (not writeable)
•
"Num resp preams" (not writeable)
•
"Distributor" (not writeable) References the company that is responsible for the distribu-
•
tion of this Field Device to customers
"Model" (not writeable) References the type of Field Device, usually an advertised model
•
number, that is unique to a single manufacturer
"Device ID" (not writeable) Uniquely identifies the Field Device when combined with the
•
Manufacturer Identification and Device Type. Therefore, this variable cannot be modified
by the Host user.
"Cfg chng count" (not writeable) This indicates the number of times the devices configura-
•
tion or calibration has been changed by a host application or from a local operator inter-
face
"Tag" is the device tag used by legacy HART 5 Communication for a unique identification.
•
26