FS24X/FS20X DTM Manual, Issue 1
"PV % rnge" is the percent value representation of "PV", scaled between "PV LRV" (0%)
•
and "PV URV" (100%)
"Loop current" is the current that floats through the 4-20mA loop.
•
"Fire detection status" is the status of the measuring
•
Device status Icon can change its colour and text, depending on the device condition
•
Second "Tab": Basic Setup
5.3.2
"Tag" is the device tag used by legacy HART 5 Communication for a unique identification.
•
Length: 8 Characters of A-Z, 0-9, [SPACE] and a selection of special characters, e.g. +, -, <,
>. Default value is "????????"
"Long tag" is the tag used by HART Communication for a unique identification.
•
Functions exactly like Tag except the size is larger (max of 32 ISO Latin 1 characters). De-
fault value is "????????????????????????????????"
"PV Snsr unit" (not writeable) is the engineering unit used by the "PV" value
•
"Distributor" (not writeable) References the company that is responsible for the distribu-
•
tion of this Field Device to customers
"Model" (not writeable) References the type of Field Device, usually an advertised model
•
number, that is unique to a single manufacturer
"Device ID" (not writeable) Uniquely identifies the Field Device when combined with the
•
Manufacturer Identification and Device Type. Therefore, this variable cannot be modified
by the Host user.
"Cfg chng count" (not writeable) This indicates the number of times the devices configura-
•
tion or calibration has been changed by a host application or from a local operator inter-
face
"Date" can be used to set a date, e.g. the date of installation or last inspection
•
"Write protect" (not writeable)
•
"Descriptor" can be used to set a short text. Length is 16 characters, allowed characters
•
are the same as for "Tag". Default value is "????????????????"
"Message" can be used to set a short text. Length is 32 characters, allowed characters are
•
the same as for "Tag". Default value is "????????????????????????????????"
"PV Snsr s/n" (not writeable) is the serial number of the sensor
•
"Final Assembly number" can be used as a unique number, to identify the device
•
"Universal rev" (not writeable) Revision of the Universal Device Description, that the Field
•
Device conforms to
"Fld dev rev" (not writeable) Revision of the Field Device Specific Device Description, that
•
the Field Device conforms to
"Software rev" (not writeable) This revision corresponds to the software or firmware, that
•
is embedded in the Field Device
25