IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Require-
ments
6.2

EMC and Environmental Type Tests

The RUGGEDCOM RX1501 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Test for IEC 61850-3
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
RUGGEDCOM RX1501
Installation Manual, 05/2020, C79000-G8976-1054-17
All manuals and user guides at all-guides.com
Test
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Con-
ducted) RFI
Magnetic Field
Voltage Dips
and Interrupts
Damped Oscillatory
Mains Frequen-
cy Voltage
Ripple on DC
Power Supply
6.2 EMC and Environmental Type Tests
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Enclosure Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
DC Power Ports
Certification
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
10 V
100 A/m, continuous
1000 A/m for 1 s
1000 A/m for 1 s
30% for 1 period
60% for 50 periods
2.5 kV common, 1 kV dif-
ferential mode @1 MHz
30 V Continuous
300 V for 1 s
10%
Severity
Levels
4
a
Note
4
4
3
4
3
a
Note
5
 
3
4
3
55