Carrier High Wall Duct Free Split System 38MVC Service Manual page 35

Comfort series high-wall duct-free split system sizes 009 - 024
Hide thumbs Also See for High Wall Duct Free Split System 38MVC:
Table of Contents

Advertisement

CHART 10 - - COMPRESSOR
Trace connections from
Trace connections from
OD board. Connections
OD board. Connections
ok?
ok?
Yes
Yes
Check contactor.*
Check contactor.*
Contactor ok?
Contactor ok?
Yes
Yes
Check capacitor.
Check capacitor.
Capacitor ok?
Capacitor ok?
Yes
Yes
Check compressor
Check compressor
windings. Ok?
windings. Ok?
No
No
Compressor ok.
Compressor ok.
* For size 9 and 12k units contactor is on outdoor board.
Check contactor output on outdoor board if not done already.
If bad, replace outdoor board.
No
No
No fix connection
No fix connection
No
No
Replace contactor
Replace contactor
No
No
Replace capacitor
Replace capacitor
No
No
Replace compressor
Replace compressor
35
A08171