Carrier High Wall Duct Free Split System 38MVC Service Manual page 28

Comfort series high-wall duct-free split system sizes 009 - 024
Hide thumbs Also See for High Wall Duct Free Split System 38MVC:
Table of Contents

Advertisement

CHART 3 - - COMPRESSOR OVERCURRENT PROTECTION
No
No
Replace compressor
Replace compressor
Is unit running in outdoor
Is unit running in outdoor
ambient higher than
ambient higher than
125 °F?
125 °F?
No
No
No
No
Outdoor coil clean?
Outdoor coil clean?
Yes
Yes
Check connections from
Check connections from
Yes
Yes
OD board. Corrosion, or
OD board. Corrosion, or
high resistance
high resistance
No
No
No
No
Outdoor fan Ok?
Outdoor fan Ok?
Yes
Yes
No
No
Connect gauges to unit.
Connect gauges to unit.
pressures ok?
pressures ok?
Yes
Yes
Check amp draw to
Check amp draw to
compressor? Values within
compressor? Values within
range?
range?
Yes
Yes
Replace outdoor board
Replace outdoor board
Beyond operating range
Beyond operating range
No
No
Clean coil.
Clean coil.
Problem persists?
Problem persists?
Yes
Yes
No
No
Clean/repair connection
Clean/repair connection
Problem persists?
Problem persists?
Yes
Yes
Change outdoor motor
Change outdoor motor
No
No
High head, high suction?
High head, high suction?
Yes
Yes
Unit is overcharged.
Unit is overcharged.
Reclaim charge and weigh
Reclaim charge and weigh
in correct charge.
in correct charge.
28
Problem solved
Problem solved
Problem solved
Problem solved
High head, low suction?
High head, low suction?
Yes
Yes
Restriction in refrigeration
Restriction in refrigeration
circuit.
circuit.
A08168