Carrier High Wall Duct Free Split System 38MVC Service Manual page 26

Comfort series high-wall duct-free split system sizes 009 - 024
Hide thumbs Also See for High Wall Duct Free Split System 38MVC:
Table of Contents

Advertisement

CHART 1 - - INDOOR FAN SPEED OUT OF CONTROL
Reset main power and
Reset main power and
restart system using remote.
restart system using remote.
Problem persists?
Problem persists?
Yes
Yes
Check motor connection.
Check motor connection.
Connection good?
Connection good?
Yes
Yes
Check IFM output and input
on indoor board.
Values good?
Yes
Yes
Replace indoor fan motor
Replace indoor fan motor
No
No
No further action is
No further action is
required
required
No
No
Fix connection
Fix connection
No
No
Replace indoor board
Replace indoor board
26
A08166